DN Item Description At shipment
F6
Presence of Application
control kit
(TCB-PCUC2E)
0000: None
0001: Exist
0000: None
d0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid 0001: Valid 0001: Valid
9A
Thermostat OFF fan
speedin cooling mode
b3 Soft cooling
0000: Remoto controller setting
0002: Fan OFF
0000: Unavailable
0001: Extremely low speed (UL)
0003: Low speed (L)
0001: Available 0001: Available
C2 Power saving 0050: 50% to 0100: 100% 0075: 75%
E0 Destination 0000: Japan 0004: Global 0004: Global
Fb Power shift 0000: Unavailable 0001: Available 0000: Unavailable
C7
Secondary heating c
Temp.(TO
H
-TO
L
)"
0000: Unavailable
0001: 1°C to 0010: 10°C
0000: Unavailable
C6
Secondary heating
Set Temp. out (high)
-0015: -15°C to 0015: 15°C 0000: 0°C
db
Secondary heating b
Temp.(TA
H-TAL)
0001: 0.5°C to 0010: 5.0°C 0006: 3.0°C
d1
8°C heating
Frost protective
operation
0000: Unavailable 0001: Available 0000: Unavailable
dc
Secondary heating a
Temp.
Normal mode (Ts-TA
H)
Flip mode (TA
L-Ts)
0000: Unavailable
0001: 1°C to 0010: 10°C
0000: Unavailable
C5
Secondary heating
mode
0000: Nomal mode 0001: Flip mode 0000: Nomal mode
77 Dual set point 0000: Unavailable 0002: Available 0000: Unavailable
0001: Extremely low
speed (UL)
120 Defrost shift 0000: Unavailable 0001: Available 0001: Available
121 Draft prevention control 0000: Unavailable 0001: Available 0001: Available
1C1 Rotation operation 0000: Unavailable 0001: Available 0000: Unavailable
1C2 Rotation interval 0001: 1 day to 0028: 28 days 0001: 1 day
1C3 Rotation lap time 0000: 0 to 0007: 70 minutes 0003: 30 minutes
1C9 Free Cooling ON Temp. -0015: -15°C to 0029: 29°C 0016: 16°C
1CA
Free Cooling OFF Temp.
-0015: -15°C to 0029: 29°C 0010: 10°C
1Cb
Free Cooling ON/OFF
differential Temp."
0000: 0 to 0010: 10°C 0002: 2°C
1C8 Free Cooling 0000: Unavailable 0001: Available 0000: Unavailable
FC
Communication
protocol *2
0000: TCC-LINK 0004: TU2C-LINK 0004: TU2C-LINK
*1 Display order of “00Un”and “0099” varies depending on remote controller models or communication types.