Toshiba RAV-HM401CTP Series - Monitor Function Data Codes; Indoor Unit Data Codes; Outdoor Unit Data Codes

Toshiba RAV-HM401CTP Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Indoor unit data
Outdoor unit data *2
CODE No. Data name Unit CODE No. Data name Unit
01
Room temperature
(Remote controller)
°C
60
61
62
63
65
6A
6D
70
72
73
F1
Outdoor heat exchanger (Coil) temperature (TE)
Outside temperature (TO)
Compressor discharge temperature (TD)
Compressor suction temperature (TS)
Heat sink temperature (TH)
Operation current (× 1/10)
Outdoor heat exchanger (Coil) temperature (TL)
Compressor operation frequency
Outdoor fan revolution frequency (Lower)
Outdoor fan revolution frequency (Upper)
Compressor calculated operation time
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm
×100h
02 Indoor suction temperature (TA) °C
03
Indoor heat exchanger (Coil)
temperature (TCJ)
°C
04
Indoor heat exchanger (Coil)
temperature (TC)
°C
B9
Communication protocol
0000: TCC-LINK, 0001: TU2C-LINK
07 Indoor fan revolution frequency rpm
F2 Indoor fan calculated operation time ×100h
F3 Filter sign time ×1h
F8 °C
Indoor unit discharge air temperature
(TF) *1
E5
Secondary heating output
- - - - : Unavailable
0000 : OFF, 0001 : ON
E6
Free cooling output
- - - - : Unavailable
0000 : OFF, 0001 : ON
E9
Rotation operation
- - - - : Unavailable
0000 : Rotation operation OFF
0001 : Rotation operation ON, Unit ON
0002 : Rotation operation ON, Unit OFF
*1 : The above temperature values are estimated from the temperature of the heat exchanger. It may differ from
the actual discharge temperature.
*2 : For outdoor unit data, refer to the Installation Manual and Service Manual of the outdoor unit.