–18–
Wiring connection
REQUIREMENT
Connect the wires matching the terminal numbers.
Incorrect connection causes a trouble.
Pass the wires through the bushing of wiring holes of
the indoor unit.
The low-voltage circuit is provided for the remote
controller. (Do not connect the high-voltage circuit)
<How to remove the electrical control box cover>
•HM56, HM80 models
Take off screws (1) and (2) at this side of the
electrical control box and remove the drip-proof
cover.
Take off screws (3) and (4) at front side of the
electrical control box and remove the electrical
control box cover.
HM90 to HM160 models
Take off screws (3) and (4) at front side of the
electrical control box and remove the cover of the
electrical control box.
(The drip-proof cover is provided to HM56 to HM80
models only.)
<Wiring>
Draw the wire into the wiring hole (knockout hole).
Attach a supplied rubber bush to the wiring hole
(knockout hole).
Be sure to fix the connecting wires using two cord
clamps as shown in the figure. Do not apply tension
on the connecting part of the terminal block.
Be sure to mount cover of the electrical control box
and the drip-proof cover.
(1)
(3)
(4)
(2)
Drip-proof cover
(HM56 to HM80
only)
Electrical control
box cover
Electrical control box
①②③
AB
<Positioning of hole for wiring (Knock-out hole) >
HM56, HM80
HM90 to HM160
Wiring hole (Knock-out hole) Wiring hole (Knock-out hole)
Earth screw
Indoor and outdoor
connecting wires
Cord clamp*
Refrigerant leak
detection sensor
Remote controller
terminal block
Power supply
terminal block
* Match the cord clamp with size of connecting wires by position of
holes on the clamp to hold the wire and fix the cord clamp by
screw.
* Be sure to fix the connecting wires using two cord clamps as
shown in the figure.
13
10
5
0
10
70
2
Indoor / Outdoor
connecting wire
Earth wire
See the figure on the above
for connecting wires to the
terminal block.
2 mm or
less
Indoor / Outdoor connecting wire
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
A
B
A
B
Terminal block
Remote
controller
unit
Terminal block for
remote controller
wiring of indoor unit
Remote controller wire
(Locally procured)
35-EN 36-EN