SERVICE MANUAL
AIR-CONDITIONER
(SPLIT TYPE)
FILE NO. SVM-13050-6
INDOOR UNIT
<Ceiling type>
RAV-SM567CTP-E (TR)
RAV-SM807CTP-E (TR)
RAV-SM1107CTP-E (TR)
RAV-SM1407CTP-E (TR)
RAV-SM1607CTP-E (TR)
SVM-13050.indb 1SVM-13050.indb 1 6/27/13 10:35 AM6/27/13 10:35 AM
Revised on Mar. 2014

Questions and Answers

  • J
    Jennifer MiddletonSep 15, 2025
    What does outdoor unit temp. sensor (TE/TS) error mean on Toshiba RAV-SM567CTP-E (TR)?
    • Z
      zwellsSep 15, 2025
      If your Toshiba Air Conditioner displays an outdoor unit temp. sensor (TE/TS) error, it means an open-circuit or short-circuit of the heat exchanger temp. sensor was detected. This is related to the Outdoor temp. sensors (TE/TS) or the outdoor P.C. board, and the entire system will stop.
  • D
    Daniel HenryAug 25, 2025
    What causes an outdoor unit fan error in a Toshiba Air Conditioner?
    • C
      Carlos JimenezAug 25, 2025
      An error (overcurrent, locking, etc.) was detected in the outdoor unit fan drive circuit. This could be due to the outdoor unit fan motor or the outdoor unit P.C. board.
  • D
    Danny BeckerAug 26, 2025
    What does it mean when the outdoor unit inverter Idc is activated in my Toshiba RAV-SM567CTP-E (TR)?
    • J
      John DoyleAug 26, 2025
      A short-circuit protection for compressor drive circuit devices (G-Tr/IGBT) was activated and this could be related to the IGBT, outdoor unit P.C. board, inverter wiring, or the compressor.
  • J
    joseschroederAug 26, 2025
    What does it mean when my Toshiba Air Conditioner displays an outdoor unit discharge temp. sensor (TD) error?
    • B
      benjamin98Aug 27, 2025
      The discharge temp. sensor has an open-circuit or short-circuit. Check the outdoor temp. sensor (TD) and the outdoor P.C. board.
  • J
    Jill PerrySep 16, 2025
    What does outdoor unit outside air temp. sensor error mean on Toshiba Air Conditioner?
    • R
      Regina HowellSep 16, 2025
      If your Toshiba Air Conditioner displays an outdoor unit outside air temp. sensor error, it means an open-circuit or short-circuit of the outdoor air temp. sensor was detected. This is related to the Outdoor temp. sensor (TO) or the outdoor P.C. board, and operation will continue.
  • T
    taylorshelbySep 23, 2025
    What does indoor unit-remote controller regular communication error mean on Toshiba RAV-SM567CTP-E (TR) Air Conditioner?
    • J
      Jessica DavisSep 23, 2025
      No data is received from the remote controller or network adapter.
  • J
    John ParkerSep 8, 2025
    What causes an outdoor unit fan error in my Toshiba RAV-SM567CTP-E (TR) Air Conditioner?
    • D
      Derek RyanSep 8, 2025
      If your Toshiba Air Conditioner displays an outdoor unit fan error, it means an error (overcurrent, locking, etc.) was detected in the outdoor unit fan drive circuit. This could be due to the outdoor unit fan motor or the outdoor unit P.C. board, and it will cause the entire system to stop.
  • A
    Andrea McgrathSep 9, 2025
    What does the fan error of the indoor unit mean on my Toshiba RAV-SM567CTP-E (TR) Air Conditioner?
    • P
      pgrossSep 9, 2025
      If your Toshiba Air Conditioner displays the fan error of the indoor unit, it indicates abnormal operation (over current or lock, etc.) is detected. This is related to the indoor fan motor or indoor P.C. board and the system will entirely stop.
  • S
    Samuel JohnsonSep 2, 2025
    What does it mean if there are duplicated header remote controllers in my Toshiba RAV-SM567CTP-E (TR) setup?
    • J
      Jason YoungSep 2, 2025
      Two remote controllers are set as header in the double-remote controller control. This is a remote controller address setting error.
  • P
    Peter YoungAug 31, 2025
    What causes a header unit follower unit regular communication error in a Toshiba RAV-SM567CTP-E (TR) Air Conditioner?
    • B
      Brett AndersonSep 1, 2025
      Regular communication is not possible between header and follower indoor units or between twin header (main) and follower (sub) units. Check the indoor P.C. board.