P33 SETTING
TRP
ti%T
33-2
RTDl
100
10%
R.TD2
100 100 100
RTD3
100 100 100
RTD4 100 100 100
RTD5
100 100 100
RTDG
100 100 100
RTD7
100 100 100
RTD8
100 100
102
I
UNIT:C
33-3
1.
.33-4
No.
Item Description
State at
delivery
33-l
Setting Sets the alarm, trip and reset levels for the
-
RTD's.
33-2
Alarm level Sets alarm detection temperature for each RTD.
100
'C
Setting range:
0
-
200
'c
33-3 Trip level
Sets trip detection temperature for each RTD.
100
'c
Setting range: 0
-
200
"c
33-4
Reset level Sets a reset temperature for each RTD. 100
'c
After the temperature goes below the reset
level. the S2E21 can then be reset.
Setting range: 0
-
200
C
-