TOSHIBA
6F9EOlll
No.
Item
Description
State at
delivery
34-3
starting
Automatically detects the starting time and
0
time
specifies whether or not the detected starting
time is used as the setting value.
Enter either 0 (OFF) or 1 (ON).
When 0 (OFF) is entered, the starting time is
displayed
(P4)
but the input setting value;
not the detected value, is used as the-setting
value in the starting time setting
(P25)..
When 1
(ON)
is entered, the detected starting
time is displayed
(P4)
and also taken as the
setting value in the starting time setting
(P25).
34-4
Heating time Automatically detects the heating time constant
0
constant
and specifies whether or not the detected value
is taken as the heating time constant setting.
When 1 (ON) is entered, the heating time
constant is automatically detected and the
detected value is taken as the setting value.
Upon completion of detection, this setting
automatically turns off.
Automatic detection requires input of
RTDl
to
RTDPfor
stator
temperature, and
RTD8
for
'
ambient temperature.
-