23-4: Setting of UC time
(TUG)
Set to 1
s.
24-2: Setting of OCG current
(IO,,)
To prevent undesired operation, Set to 10
(%).
24-3: Setting of OCG time
(TO&
Set to 0.1 s.
25-2: Setting of allowable locking time in cold condition
(TSC)
Given value (Consult motor manufacturer>
25-3: Starting current
(1st)
See motor data.
Or after one start, read screen P4. (See page
50.4-2.)
25-4: Starting time
(Tst)
Varies per application. (motor, load,type of starter)
-
calculate based on motor torque and load .
-
Or after one start, read screen P4. (See page
50.4-4.)
-..
--