Toshiba Super MMY-MAP0801HT7 - Indoor Other Error; Outdoor EEPROM Error

Toshiba Super MMY-MAP0801HT7
270 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
169
Check code name
[F29] / [12]
(d07 / AI-NET)
Check code name
Indoor other error
Cause of operation
Indoor P.C. board error
EEROM error
This error is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on indoor unit P.C.
board. Replace service P.C. board.
If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write EEPROM data,
the automatic address mode is repeated. In this case, [97 error] is displayed on AI-NET central controller.
Check code name
[F31] / [1C]
(d07 / AI-NET)
Check code name
Outdoor EEPROM error
Cause of operation
1. Outdoor unit power error (Voltage, noise, etc.)
2. Outdoor I/F P.C. board error
(Approx. 3 minutes) (Approx. 1 minute)
(Power ON) [SET DATA] is displayed
on main remote controller.
[SET DATA]
disappears.
LED (D02) 1Hz flashes
for approx. 10 seconds
on indoor unit P.C. board.
Repeat
(Reset)
(Repetition)
Check I/F P.C. board.
NO
YES
Check power voltage and line.
Correct power line.
Check external noise, etc.
Is there any trouble of
outdoor unit power supply?