<Installation of compressor>
Install the compressor in the reverse procedure of removal.
When removing the compressor, Fasten receptacle terminals of the compressor may be loosened.
Prior to the installation, caulk a little to them with radio pinchers, reinsert them into the compressor,
and then check there is no looseness.
(NOTES)
Only two hexagonal bolts are provided to a compressor, but it is not lacking.
The tightening torque of the hexagonal bolt to fix the compressor is 200kg/cm.
If oil has been extracted from the accumulator, braze the cutoff pipe after pinching.
<Vacuuming>
(In case of single outdoor system>
Connect vacuum pump to the valve charge ports of the liquid and gas pipes and the check joint at high-
pressure side, and then drive the vacuum pump.
Vacuum until the vacuum low-pressure gauge indicates 1 (mmHg).
(NOTE)
Before vacuuming, open PMV fully. Vacuuming may not be executed for the heat exchanger of the outdoor
unit under condition of PMV closed.
(In case of multiple outdoor units system)
In case of conducting the refrigerant recovery at replacing the compressor, perform vacuuming as
13-3. Process after repair.
<Full opening of PMV>
Turn on power of the outdoor unit.
Short CN30 on I/F P.C. board of the outdoor unit.
Turn off power of the outdoor unit within 2 minutes after short-circuiting.
<Refrigerant charging>
Add the same amount of refrigerant as the remaining refrigerant refrigerant from the charge port of the
service valve at liquid side.