2. Indoor unit setup in Specific indoor unit priority mode
The setup can be changed during stop of operation. (Be sure to stop the system.)
Operation contents
When pushing
SET
+
CL
+ buttons at the same time for 4 seconds or more, as shown in the figure,
the display section flashes after a while confirm the displayed item code is [

].
When the item code is one other than [

], push button to
eliminate the display and then repeat the procedure from the first step.
(The remote controller operation is not accepted approx. 1 minute
after pushing
button.)
(In a group control, the indoor unit with number displayed firstly is set to
the header unit.)
Every pushing
UNIT
, the indoor unit numbers in the group control are successively displayed.
Select the indoor unit of which setup is to be changed.
In this time, as the fan and louver of the selected indoor unit operate,
the position of the indoor unit of which setup is to be changed can be confirmed.
Using the setup temperature and buttons, specify the item code [
"
].
Using the timer time and buttons, select the setup data [

].
Priority:

, No priority:

Push
SET
button. In this time, the setup operation finishes when the display changes from flashing to
lighting.
After setup operation has finished, push button. (Setup is determined.)
When pushing button, the display disappears and the status returns
to the usual stop status.
(The remote controller operation is not accepted for approx. 1 minute.)
(NOTE)
Only one indoor unit can be set to Priority. If the multiple indoor units are accidentally set to Priority, an error
code (L05 or L06: Duplicated indoor unit priority) is displayed.
To the unit displaying L05, [0001 (Priority)] is setup. Separate a unit which you will give priority from the other
indoor units, and return the setup data of the other indoor units to [0000 (No priority)].
Procedure
1
2
3
4
5
6
Error code
L05
L06
Error contents
Indoor unit priority duplication ([

] is set up.)
Indoor unit priority duplication ([

] is set up.)
1
5
4
6
2
3
UNIT
SET
CL
UNIT No.
CODE No.
SET DATA
R.C. No.
UNIT No.
CODE No.
SET DATA
R.C. No.
UNIT No.
CODE No.
SET DATA
R.C. No.