■Dx-Coil design guideline
•AHU / DX-Coil Notes & Features:-
Cooling & Heating output figures are based on calculations and ‘general’ test data. All figures are to be taken as
approximations. The properties of the 3
rd
Party DX-Coil will have an effect on the performance of the Outdoor units.
The DX Coil must be suitable for R410A.
The design should allow operation as both an Evaporator and a Condenser
(Features: Multiple circuits / Liquid Capillary Distributor / Gas Header)
The counter flow principle must be observed for the DX coil design
A Drain Pan must be fitted (even if only used in Heat mode) due to defrost cycles
It is recommended to fit droplet eliminator plates in the discharge air stream if used
in cooling mode.
• Dx-coil design guideline
Be sure to refer to the guideline for 3
rd
party Coil and AHU design to ensure the operation.
Coil internal
volume
(inch
3
)
Number
of circuits
by U-Pipe
diameter
Distributor Orifice
size (ID inch)
Design evaporating
temperature
Evaporator air suction
temp.
Design condensing
temperature
Condenser air suction
temp.
Cooling ”Air ON” temp.
(*1)
Heating ”Air ON” temp.
(*1)