E6581288
− 7 
4.2. Inverter parameter (relate to the CC-Link)
Title Function Description
f
850
Disconnection detection
extended time
0.0
to
100.0
sec.
f
851
Inverter operation at
disconnection
0
:
Stop and Communication release (by
cmod
,
fmod
)
1
:
None (continued operation)
2
:
Deceleration stop
3
:
Coast stop
4
:
Network error(
err8
trip)
5
:
Preset speed operation (by
f852
setting)
f
852
Preset speed operation
selection
0
:
None
1
to
15
:
Preset speed operation (by parameter setting)
f
853
Communication option
station address monitor
(Read only)
Station No.
1
to
64
(case by CC-Link option)
f
854
Communication option
speed switch monitor
(Read only)
0
:
156kbps
1
:
625kbps
2
:
2.5Mbps
3
:
5Mbps
4
:
10Mbps
f
899
Network option reset
setting
0
:
None
1
:
Reset option circuit board and inverter
Version check of option card CPU
The version of the option with it has equipped can be checked by using the function of
f710tof718 (standard monitor display selection).
*For details, refer to Instruction Manual E6581301.
Title Function Setting Description
32
Add-on option 1 CPU version
(Under side option)
f710
f718
Standard display
monitor
33
Add-on option 2 CPU version
(Panel side)
For example, a panel display shown 1.02, when a CPU version is 1 (01H) and revision is 2
(02H).

Other manuals for Toshiba TOSVERT VF-AS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS1
CategoryInverter
LanguageEnglish

Related product manuals