4.2. Inverter parameter (relate to the CC-Link)
Title Function Description
f
850
Disconnection detection
extended time
0.0
to
100.0
sec.
f
851
Inverter operation at
disconnection
0
:
Stop and Communication release (by
cmod
,
fmod
)
1
:
None (continued operation)
2
:
Deceleration stop
3
:
Coast stop
4
:
Network error(
err8
trip)
5
:
Preset speed operation (by
f852
setting)
f
852
Preset speed operation
selection
0
:
None
1
to
15
:
Preset speed operation (by parameter setting)
f
853
Communication option
station address monitor
(Read only)
Station No.
1
to
64
(case by CC-Link option)
f
854
Communication option
speed switch monitor
(Read only)
0
:
156kbps
1
:
625kbps
2
:
2.5Mbps
3
:
5Mbps
4
:
10Mbps
f
899
Network option reset
setting
0
:
None
1
:
Reset option circuit board and inverter
■Version check of option card CPU
The version of the option with it has equipped can be checked by using the function of
f710tof718 (standard monitor display selection).
*For details, refer to Instruction Manual E6581301.
Title Function Setting Description
32
Add-on option 1 CPU version
(Under side option)
f710
f718
Standard display
monitor
33
Add-on option 2 CPU version
(Panel side)
For example, a panel display shown 1.02, when a CPU version is 1 (01H) and revision is 2
(02H).
〜