EasyManua.ls Logo

Toshiba TOSVERT VF-nC1 - Undervoltage Trip

Toshiba TOSVERT VF-nC1
143 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581090
F-25
6
<Example of operation>
1) If function 12 (OT: over-torque detection) is assigned to the FM/OUT terminal,
using the output terminal selection parameter H
H (FM/OUT terminal selection 1): 12 (OT: over-torque detection)
Time (sec)
H
-10%
H
Torque current (%)
Over-torque-
detection signal
P15-FM/OUT
H
ON
FF
OFF
*The VF-nC1 inverter has 10% of hysteresis to prevent the occurrence of over-torque hunting.
Therefore, the over-torque signal is turned off at a level lower than the setting of
H
by
10% (hysteresis).
Less than
H
-set value
6.14.8 Undervoltage trip
H
: Under voltage trip selection
Function
This parameter is used to select the control mode activated when an undervoltage is
detected. The error message
WR
will be displayed if the inverter trips because of an
undervoltage.
H : Disabled ・・・・The inverter shuts down but not trip. (FL relay not activated) The
inverter shuts down if the voltage drops below 64% of the rated
voltage.
H : Enabled ・・・・・The inverter shuts down. It trips if the voltage drops below 64% of
the rated voltage. (FL relay activated)
H : Disabled ・・・・The inverter shuts down but not trip. (FL relay not activated) The
inverter shuts down if the voltage drops below 50% of the rated
voltage. When setting H to , be sure to install the input
reactor of an option.
Title FunctionAdjustment rangeDefault setting
H
Under voltage trip
selection
0: Disabled
1: Enabled (shutdown below 64%,
FL relay activated)
2: Disabled (shutdown below 50%,
FL relay not activated)
0

Table of Contents

Related product manuals