6.14.9 Analog input disconnection detection
H
: Analog input disconnection detection
Function
This parameter is used to detect a break in an analog signal to the VI/S3 terminal. If an analog
signal is below the level set with
H
for 0.3 seconds (approx.), the inverter will assume the
signal to be broken and it will trip and display the error message “
G
.” (The Analog input
disconnection detection function is disabled if
H
is set to 0.0%.)
Title FunctionAdjustment rangeDefault setting
H
Analog input
disconnection detection
0: Disabled
1~100%
0
6.15 Operation panel parameters
6.15.1 Prohibiting the change of parameter settings
H : Prohibition of change of parameter settings
Function
This parameter specifies whether parameter setting is changeable or not.
Setting methods
[Parameter setting]
Title FunctionAdjustment range Default setting
H
Prohibition of
change parameter
settings
0~7 (See the explanation below.)
: Permitted
_____
EOQF and HOQF settings cannot be changed during operation. (Default)
: Prohibited
_____
All parameters are read/write-protected.
: Permitted
_____
EOQF and HOQF settings also can be changed during operation.
: Prohibited
_____
Frequency can be changed from the operation panel but all other
parameters are read/write-protected.
: Permitted
_____
The emergency stop function cannot be controlled from the operation panel
and EOQF and HOQF settings cannot be changed during operation.
: Prohibited
_____
The emergency stop function cannot be controlled from the operation panel
but all parameters are read/write-protected.
: Permitted
_____
The emergency stop function cannot be controlled from the operation panel
and EOQF and HOQF settings also can be changed during operation.
: Prohibited
_____
The emergency stop function cannot be controlled from the operation panel,
frequency can be changed on the operation panel, but any other parameters
are write/read-protected.
Note: Some parameters cannot be changed during operation, no matter how H is set. (See
4.1.4.)
Canceling the setting
Only the setting of H can be changed anytime, no matter how it is set.