E6581913
48
Com-
munica-
tion
Number.
Title Function Adjustment range Unit
Default
setting
Valid Reference
0870
f870
Block write data 1
0871
f871
Block write data 2
0: No selection
1: Communication command 1
(FA00)
2: Communication command 2
(FA20)
3: Frequency command value
(FA01)
4: Output data on the terminal
board (FA50)
5: FM analog output (FA51)
6: Motor speed command (FA13)
- 0 After reset.
0875
f875
Block read data 1
0876
f876
Block read data 2
0877
f877
Block read data 3
0878
f878
Block read data 4
0879
f879
Block read data 5
0: No selection
1: Status information 1 (FD01)
2: Output frequency (FD00)
3: Output current (FD03)
4: Output voltage (FD05)
5: Alarm information (FC91)
6: PID feedback value (FD22)
7: Input terminal monitor (FD06)
8: Output terminal monitor (FD07)
9: Terminal VIA monitor (FE35)
10:Terminal VIB monitor (FE36)
11:Terminal VIC monitor (FE37)
12:Input voltage (FD04)
13:Motor speed (FE90)
14:Torque (FD18)
- 0 After reset.
Section
4.1.3
5.1.2
5.1.5
5.1.6
0880
f880
Free notes 0-65535 1 0 Real time
Section
7.5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com