12
Smart Switch
Note: The grounding bar and the ground cable are not provided with our product. If 
needed, please self purchase them.
Connecting to the Ground via the Power Supply
 
If the device is installed in the normal environment, the device can be grounded via the 
PE (Protecting Earth) cable of the AC power supply as shown in the following figure.
Connecting to the GroundFigure 3-2 
Note: 
The figure is to illustrate the application and principle. The power plug you get from 
 
the package and the socket in your situation will comply with the regulation in your 
country, so they may differ from the figure above.
If you intend to connect the device to the ground via the PE (Protecting Earth) cable 
 
of AC power cord, please make sure the PE (Protecting Earth) cable in the electrical 
outlet is well grounded in advance.
Equipotential Bonding is the practice of intentionally electrically connecting all earthed 
systems  to  the  same  grounding grid  or  connecting  the  grounding  grids  of  all  the 
earthed systems  together through  the ground or overground  metal  so  as  to  create 
an earthed equipotential  zone.  When  lightning occurs, the high voltage produced by 
lightning  current in all systems will meanwhile exist in their ground cables, and thus 
all ground cables have the same electrical potential and basically eliminate the electric 
strikes between the systems.
The figure below illustrates how to practice equipotential bonding in a network. 
Lightning Protection