37
4YCC4042E1060
EXTERNAL STATIC PRESSURE (IN.WG)
Horizontal Airflow [Down Airflow]
Motor Speed
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Constant
Circulation
CFM
APPROXIMATELY 40-50% COOLING OR HEATING AIRFLOW
WATTS
Cooling - Low
CFM
1358
(1345)
1393
(1379)
1348
(1334)
1296
(1283)
1253
(1241)
- - - - - -
WATTS
224
(228)
233
(238)
242
(247)
252
(257)
262
(267)
- - - - - -
Cooling - Med
CFM
1521
(1506)
1490
(1475)
1448
(1433)
1391
(1377)
1362
(1348)
1338
(1325)
1315
(1302)
1307
(1293)
1254
(1241)
- -
WATTS
306
(312)
316
(322)
327
(333)
337
(344)
348
(354)
359
(366)
369
(377)
382
(389)
395
(403)
- -
Cooling - High
CFM - - - -
1529
(1514)
1491
(1476)
1467
(1453)
1425
(1411)
1385
(1371)
1345
(1331)
-
WATTS - - - -
455
(464)
467
(477)
477
(487)
490
(499)
503
(513)
513
(523)
-
Heating - Low
CFM
1104
(1109)
1042
(1047)
977
(982)
911
(916)
841
(845)
764
(767)
687
(690)
598
(601)
- - -
WATTS
109
(109)
116
(117)
124
(125)
134
(134)
142
(143)
152
(153)
161
(162)
171
(172)
- - -
Heating - High
CFM -
1171
(1177)
1112
(1117)
1050
(1055)
990
(995)
927
(931)
821
(856)
779
(783)
704
(707)
- -
WATTS -
154
(155)
162
(163)
172
(173)
182
(182)
192
(193)
203
(204)
214
(215)
225
(226)
- -
Note: Cooling airflow must not exceed 1575 CFM due to condensate blowoff.
4YCC4042E1090
EXTERNAL STATIC PRESSURE (IN.WG)
Horizontal Airflow [Down Airflow]
Motor Speed
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Constant
Circulation
CFM
APPROXIMATELY 40-50% COOLING OR HEATING AIRFLOW
WATTS
Cooling - Low
CFM
1358
(1345)
1393
(1379)
1348
(1334)
1296
(1283)
1253
(1241)
- - - - - -
WATTS
224
(228)
233
(238)
242
(247)
252
(257)
262
(267)
- - - - - -
Cooling - Med
CFM
1521
(1506)
1490
(1475)
1448
(1433)
1391
(1377)
1362
(1348)
1338
(1325)
1315
(1302)
1307
(1293)
1254
(1241)
- -
WATTS
306
(312)
316
(322)
327
(333)
337
(344)
348
(354)
359
(366)
369
(377)
382
(389)
395
(403)
- -
Cooling - High
CFM - - - -
1529
(1514)
1491
(1476)
1467
(1453)
1425
(1411)
1385
(1371)
1345
(1331)
-
WATTS - - - -
455
(464)
467
(477)
477
(487)
490
(499)
503
(513)
513
(523)
-
Heating - Low
CFM
1419
(1426)
1380
(1387)
1341
(1348)
1295
(1301)
1249
(1255)
1204
(1210)
1160
(1166)
1115
(1120)
1069
(1074)
1015
(1020)
961
(966)
WATTS
240
(241)
250
(251)
259
(260)
269
(270)
279
(281)
291
(292)
302
(303)
312
(314)
323
(325)
333
(335)
348
(349)
Heating - High
CFM
1559
(1567)
1524
(1531)
1483
(1491)
1443
(1450)
1401
(1408)
1363
(1370)
1319
(1326)
1276
(1282)
1233
(1239)
1195
(1201)
1147
(1152)
WATTS
313
(315)
324
(325)
335
(337)
346
(347)
356
(358)
367
(368)
379
(381)
392
(394)
403
(405)
415
(417)
428
(430)
Note: Cooling airflow must not exceed 1575 CFM due to condensate blowoff.
UUnniitt SSttaarrttuupp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Technologies 4YCC4030E1070A and is the answer not in the manual?

Trane Technologies 4YCC4030E1070A Specifications

General IconGeneral
BrandTrane Technologies
Model4YCC4030E1070A
CategoryAir Handlers
LanguageEnglish

Related product manuals