18-EB40D1-1A-EN
39
4YCC4060E1090
EXTERNAL STATIC PRESSURE (IN.WG)
Horizontal Airflow [Down Airflow]
Motor Speed
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Constant
Circulation
CFM
APPROXIMATELY 40-50% COOLING OR HEATING AIRFLOW
WATTS
Cooling - Low
CFM
1857
(1831)
1831
(1802)
1800
(1765)
1766
(1728)
- - - - - - -
WATTS
515
(524)
523
(533)
533
(545)
544
(558)
- - - - - - -
Cooling - Med
CFM
2031
(2003)
2003
(1975)
1974
(1946)
1940
(1913)
1907
(1880)
1874
(1848)
1837
(1811)
1805
(1780)
1771
(1746)
- -
WATTS
594
(611)
609
(627)
624
(642)
639
(658)
653
(672)
667
(686)
681
(701)
695
(715)
709
(730)
- -
Cooling - High
CFM
2083
(2054)
2058
(2030)
2032
(2010)
2003
(1976)
1974
(1946)
1943
(1911)
1911
(1879)
1877
(1848)
1843
(1817)
1807
(1781)
-
WATTS
749
(770)
759
(781)
769
(790)
779
(804)
788
(819)
803
(832)
816
(845)
830
(858)
845
(872)
860
(887)
-
Heating - Low
CFM
1534
(1541)
1489
(1497)
1445
(1452)
1403
(1410)
1361
(1367)
1314
(1321)
1275
(1281)
1234
(1240)
- - -
WATTS
281
(282)
292
(293)
304
(305)
314
(316)
325
(327)
337
(339)
348
(349)
358
(360)
- - -
Heating - High
CFM -
1594
(1602)
1551
(1558)
1511
(1518)
1471
(1478)
1430
(1437)
1386
(1392)
1344
(1351)
1305
(1311)
1265
(1271)
-
WATTS -
348
(350)
361
(363)
373
(374)
384
(386)
396
(398)
409
(411)
420
(423)
432
(434)
443
(445)
-
Note: Cooling airflow must not exceed 2250 CFM due to condensate blowoff.
4YCC4060E1115
EXTERNAL STATIC PRESSURE (IN.WG)
Horizontal Airflow [Down Airflow]
Motor Speed
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Constant
Circulation
CFM
APPROXIMATELY 40-50% COOLING OR HEATING AIRFLOW
WATTS
Cooling - Low
CFM
1857
(1831)
1831
(1802)
1800
(1765)
1766
(1728)
- - - - - - -
WATTS
515
(524)
523
(533)
533
(545)
544
(558)
- - - - - - -
Cooling - Med
CFM
2031
(2003)
2003
(1975)
1974
(1946)
1940
(1913)
1907
(1880)
1874
(1848)
1837
(1811)
1805
(1780)
1771
(1746)
- -
WATTS
594
(611)
609
(627)
624
(642)
639
(658)
653
(672)
667
(686)
681
(701)
695
(715)
709
(730)
- -
Cooling - High
CFM
2083
(2054)
2058
(2030)
2032
(2010)
2003
(1976)
1974
(1946)
1943
(1911)
1911
(1879)
1877
(1848)
1843
(1817)
1807
(1781)
-
WATTS
749
(770)
759
(781)
769
(790)
779
(804)
788
(819)
803
(832)
816
(845)
830
(858)
845
(872)
860
(887)
-
Heating - Low
CFM
1827
(1815)
1792
(1790)
1757
(1757)
1721
(1712)
1685
(1679)
1646
(1648)
1605
(1613)
1570
(1574)
- - -
WATTS
492
(510)
505
(520)
517
(532)
529
(549)
541
(560)
553
(570)
566
(582)
577
(596)
- - -
Heating - High
CFM -
1927
(1910)
1894
(1875)
1861
(1839)
1824
(1803)
1788
(1773)
1750
(1736)
1711
(1704)
1674
(1661)
1639
(1622)
-
WATTS -
614
(630)
627
(634)
639
(647)
651
(660)
664
(672)
677
(685)
689
(698)
702
(712)
715
(726)
-
Note: Cooling airflow must not exceed 2250 CFM due to condensate blowoff.
UUnniitt SSttaarrttuupp