BAS-SVX44C-EN 37
Other Thermostat Functions
The programmable thermostat has other functional features which provide more flexibility and control in
its operation. Those features are:
Heat/Cool indicator display (for both programmable and non-programmable thermostats (refer to the
next section,
“Heat/Cool Indicator Display” )
Non-programmable mode
Filter change
Clean screen
Local/remote/outdoor temperature display and control
Local/remote humidity display and control
System lock
Heat/Cool Indicator Display
Setpoint display: when the system is set for only Heat or only Cool, there is no flame ( ) or snowflake
( ) icon under the setpoint value.
When the system is set to AUTO ( ), the following applies:
When the thermistor used for H/C control is above the Cool Setpoint, the Cool Setpoint will show on
the display along with the snowflake ( ) under the setpoint.
When the thermistor used for H/C control is below the Heat Setpoint, the Heat Setpoint will show on
the display along with the flame (
) under the setpoint.
When the thermistor used for H/C control is between the Cool and Heat Setpoints (inclusive), the last
active system setpoint (Cool or Heat) will show on the display.
When the system is set to AUTO ( ), the blink rates for the snowflake ( ) and flame ( ) under
the setpoint are as follows:
When no Cool or Heat cycle is running and no compressor protection timer running, if the Heat
Setpoint is showing, then the flame (
) under the setpoint will blink at 4.5 seconds ON and 1.75
seconds OFF.
When no Cool or Heat cycle is running and no compressor protection timer running, if the Cool Setpoint
is showing, then the snowflake ( ) under the setpoint will blink at 4.5 seconds ON and 1.75 seconds
OFF.
When Cool cycle is running, then the snowflake ( ) under setpoint should be solid.
When Heat cycle is running, then the flame ( ) under setpoint should be solid.
When the compressor timer is running before Cool cycle, then the snowflake ( ) under setpoint
should blink 1.5 seconds ON and 0.5 second OFF.
When the compressor timer is running before Heat cycle, then the flame ( ) under setpoint should
blink 1.5 seconds ON and 0.5 second OFF.