BAS-SVX44C-EN 45
Temperature Cycle Control
Figure 23. Auto 3/heat and 2/cool systems
General Notes:
The third auxiliary-stage heat output is only used for 3H/2C heat pump systems.
The algorithm of cycling control is the same as the first-stage output. However, it has independent cycle
period setting.
Both the first and second stage use the same temperature differential around setpoint for cycling
control.
When the system is set for 3H/2C HP, the cycles for auxiliary heat (Option Number 0164) is used for
the third auxiliary heat stage.