BAS-SVX44C-EN 49
Other Functional Components
There is a minimum 5°F (2.5°C) deadband between compressor and auxiliary heat lockout temperatures.
Configuration option #220 sets the compressor lockout point; #221 sets the auxiliary lockout point. Refer
to the following illustrations.
Aux Lockout
Temperature
IPN 0221=0
Compr Lockout
Temperature
IPN0220≠0
Auxiliary H eat Only
Both C om pressor H P
and Auxiliary Heat
O
u
t
d
o
o
r
T
e
m
p
e
r
a
t
u
r
e
15 to 45F (-9.5 to 7.0C)
IPN0210 =2 (Heat Pump Operation
with only Compr Lockout )
Aux Lockout
Temperature
IPN0221≠0
Compr Lockout
Temperature
IPN 0220=0
Both C om pressor H P
and Auxiliary Heat
Compressor HP Only
O
u
t
d
o
o
r
T
e
m
p
e
r
a
t
u
r
e
40 to 60F (4.5 to 15.5C)
IPN0210 =2 (Heat Pump Operation
with only Aux Lockout)
Aux Lockout
Temperature
IPN0221≠0
Compr Lockout
Temperature
IPN0220≠0
Auxiliary H eat Only
Both C om pressor H P
and Auxiliary Heat
Compressor HP Only
O
u
t
d
o
o
r
T
e
m
p
e
r
a
t
u
r
e
40 to 60F (4.5 to 15.5C)
15 to 45F (-9.5 to 7.0C)
IPN0210 =2 (Heat Pump Operation
with Compr and Aux Lockout)
Both Compressor and Auxiliary
Lockout Enabled
Compressor Lockout Disabled and
Auxiliary Lockout Enabled
Compressor Lockout Enabled and
Auxiliary Lockout Disabled

Table of Contents