TK 62061-18-IM-EN
55
CP2 Compartments Priority modulation, time OFF (min)
Modulation timer: (Only Priority compartment ON)
Selectable from 1 to 30 minutes. Default is 10 minutes.
While CP2 is counting, only priority compartment is ON (COOL/HEAT)
Non priority compartment is in NULL mode
10 1 30
dAL Out of range alarm
Programmable from 1º up to 10º or off (0). When the return air temperature
exceeds set point, the on-screen return air temperature reading flashes.
0 0 10
HC
Hour Counter initial value for maintenance purposes
(tens of hours, e.g. 150=1500 hours), programmable from 1000 up to 5000,
500 steps.
150 0 500
dSP Doors Switches Presence/Polarity
0: normally closed, 1: normally open, 2: not present.
1 0 2
bE Buzzer Enable
0: not enabled, 1: enabled, 2: enabled also when keys are pressed, 3:
enabled only when keys are pressed.
2 0 3
tu Thermostat units
C: temperature visualization in ºC, F: temperature visualization in ºF.
C C F
Pu Pressure units
b: pressure visualization in bar, P: pressure visualization in psi.
P b P
trE Temperature display resolution
0: whole; 1: resolution 0.5; 2: resolution: 0.1
0 0 2