Loading...
VAV-SVX08U-EN
13
Digit 27, 28, 29— Electric Heat kW
000 = None
010 = 1.0 kW
015 = 1.5 kW
460 = 46.0 kW
Notes:
0.5 to 8.0 kW in 1/2 kW
increments
8.0 to 18.0 kW in 1 kW
increments
18.0 to 46.0 kW in 2 kW
increments
Digit 30 Electric Heat Stages
0 = None
1 = 1 Stage
2 = 2 Stages Equal
3 = 3 Stages Equal
Note: Digit 3 not available with low height.
Digit 31 Electric Heat Contactors
0 = None
1 = 24V Magnetic
5 = 0-10 Vdc SCR Heat; UC400
6 = 0-10 Vdc SCR Heat; FMTD/ENCL/DD00
7 = 24V SSR (Solid State Relay)
Notes: SCR cannot be selected with the
following:
kW>10,208V, 3Ph, Low Height
kW>22,480V, 3Ph, Low Height
Voltage = 575V
Digit 32— Air Switch
0 = Not Applicable
W = With
Digit 33— Not Used
0 = Not Applicable
Digit 34 Actuator
0 = Standard
A = Belimo Actuator
G = Trane Analog Actuator (UC210 or UC400
only)
Digit 35 Wireless Sensors
0 = None
3 = Trane Air-Fi® Wireless Communications
Interface
Note: All sensors selected in accessories.
Digit 36 Pre-wired Factory
Solutions
0 = None
1 = Factory-mounted DTS
2 = HW Valve Harness
3 = Both DTS/HW Valve Harness
Digit 37 Bottom Access
0 = None
W = Access Left Side Terminal Unit
Digit 38 —Piping Package
0 = None
A = 2–Way Automatic Balancing
B = 3–Way Automatic Balancing
C = 2-Way Standard Valve Only, Floating
Point Actuator
D = 3-Way Standard Valve Only, Floating
Point Actuator
E = 2-Way Standard Valve Piping Package,
Floating Point Actuator
F = 3-Way Standard Valve Piping Package,
Floating Point Actuator
G = 2-Way Belimo Valve Only, Floating Point
Actuator
H = 3-Way Belimo Valve Only, Floating Point
Actuator
J = 2-Way Belimo Valve Piping Package,
Floating Point Actuator
K = 3-Way Belimo Valve Piping Package,
Floating Point Actuator
L = 2-Way Belimo Valve Only, Analog
Actuator
M = 3-Way Belimo Valve Only, Analog
Actuator
N = 2-Way Belimo Valve Piping Package,
Analog Actuator
P = 3-Way Belimo Valve Piping Package,
Analog Actuator
Digit 39 Water Valve
0 = None
1 = Trane HW Valve 0.7 Cv
2 = Trane HW Valve 2.7 Cv
5 = Analog HW Valve, Field Provided (UC210
or UC400 only)
6 = Trane HW Valve 1.7 Cv
7 = Trane HW Valve 5.0 Cv
A = Belimo HW Valve, 0.3 Cv
B = Belimo HW Valve, 0.46 Cv
C = Belimo HW Valve, 0.8 Cv
D = Belimo HW Valve, 1.2 Cv
E = Belimo HW Valve, 1.9 Cv
F = Belimo HW Valve, 3.0 Cv
G = Belimo HW Valve, 4.7 Cv
Digit 40 Flow Rate
0 = None
A = 0.5 gpm, 0.03 l/s
B = 1.0 gpm, 0.06 l/s
C = 1.5 gpm, 0.09 l/s
D = 2.0 gpm, 0.13 l/s
E = 2.5 gpm, 0.16 l/s
F = 3.0 gpm, 019 l/s
G = 3.5 gpm, 0.22 l/s
H = 4.0 gpm, 0.25 l/s
J = 4.5 gpm, 0.28 l/s
K = 5.0 gpm, 0.31 l/s
L = 5.5 gpm, 0.35 l/s
M = 6.0 gpm, 0.38 l/s
N = 6.5 gpm, 0.41 l/s
P = 7.0 gpm, 0.44 l/s
Q = 7.5 gpm, 0.47 l/s
MMooddeell NNuummbbeerrss