EasyManua.ls Logo

Trane Technologies Voyager 3 - User Manual

Trane Technologies Voyager 3
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment
can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
November 2022
RT-SVX34V-EN
Installation, Operation, and Maintenance
Voyager™ 3
Packaged Rooftop Air Conditioners with Symbio™
700 Controls
27.5 to 50 Tons - 60 Hz
22.9 to 41.7 Tons (82-142 kW) - 50 Hz
“C” and later design
sequence
60Hz/3 phase: TC*,
TE*, YC*, 330C, 360C,
420C, 480C, 600C
50 Hz/3 phase: TC*,
TE*, YC*, 275C, 305C,
350C, 400C, 500C

Questions and Answers

  • J
    jill60Sep 3, 2025
    Why Trane Technologies Air Conditioner will not heat or cool, but the fan switch operates?
    • S
      Steven ThomasSep 3, 2025
      If your Trane Technologies Air Conditioner's fan switch works, but it's not heating or cooling, it could be due to: * A defective Zone Sensor Module (ZSM). Refer to the Zone Sensor Module (ZSM) Test Procedures. * A problem in the ZSM wiring. Disconnect the ZSM wiring at the RTRM and test the wires using the Zone Sensor Test Procedures to locate any wiring problems.
  • S
    Shawn HaleSep 19, 2025
    Why Trane Technologies Voyager 3 Air Conditioner minimum position is at zero, cannot be adjusted?
    • J
      Jason Herrera MDSep 19, 2025
      If the minimum position on your Trane Technologies Air Conditioner is at zero and cannot be adjusted, it's possible that the remote Minimum position potentiometer has failed. With the main power off, check the resistance between terminals on J8 at the Customer Connection Module by rotating the remote minimum position potentiometer knob. Resistance should be 50 to 200 Ohms.
  • M
    Marco BurkeSep 16, 2025
    Why Trane Technologies Air Conditioner will not heat (YC’s only): GV does not energize, CFM runs, igniter sparks?
    • Z
      zacharyortizSep 16, 2025
      If your Trane Technologies Air Conditioner (YC’s only) isn't heating, and the GV doesn't energize, but the CFM runs and the igniter sparks, here's what to check: * There may be a wiring or terminal failure. Verify the presence of 24 VAC between the IGN J1-7 terminal to ground. If not present, check the wiring and terminals and repair or replace if necessary. * The GV may have failed. Measure the voltage between TH and TR on the gas valve (GV). If 24 VAC is present and the GV will not open, replace the GV. * There may be a pressure switch failure. Verify that the input gas pressure is not below the minimum set on the low gas pressure switch.
  • J
    josephhartmanSep 14, 2025
    Why Trane Technologies Voyager 3 will not heat (YC’s only): CFM runs, GV energizes, igniter does not spark?
    • C
      Christian WoodwardSep 14, 2025
      If your Trane Technologies Air Conditioner (YC’s only) isn't heating, and the CFM runs, the GV energizes, but the igniter doesn't spark, consider the following: * The flame sense rod may have failed. Check for continuity between the rod and ground and replace the flame sense rod if there is no continuity. * There may be a wiring or terminal failure. Check wiring and terminals and repair or replace if necessary. * The spark igniter may have failed. The spark igniter should fire when heat is called for and 155VAC is applied. If no spark, replace the igniter. * The high temp limit switch may have failed. Check for continuity across the high temp limit switch and replace if there is no continuity.
  • J
    James CaldwellSep 12, 2025
    What to do if Trane Technologies Voyager 3 power exhaust fan cycles on and off?
    • E
      Eric BrooksSep 12, 2025
      If the power exhaust fan on your Trane Technologies Air Conditioner is cycling ON and OFF, it could be due to: * The Space Pressure Deadband being too narrow. Increase the Space Pressure Deadband. * The Space Pressure Setpoint being too high or low. Verify Building Pressure with maximum building exhaust enabled. Adjust Space Pressure Setpoint accordingly.
  • S
    Sonia AndersonSep 12, 2025
    Why Trane Technologies Air Conditioner will not heat (YC’s only): CFM will not run, igniter sparks, GV is energized?
    • E
      Emily LeonardSep 12, 2025
      If your Trane Technologies Air Conditioner (YC’s only) isn't heating, and the CFM won't run, but the igniter sparks and the GV is energized, check these items: * The CFM may have failed. Check the CFM and replace if necessary. * The CFM capacitor may have failed. Disconnect the BROWN wires from the capacitor, test it, and replace it if necessary. * There may be a wiring or terminal failure. Check the wiring and terminals and repair or replace if necessary. * TNS3 and/or 4 may have failed (460/575 V units only). Check for 230 VAC at TNS3 and/or 4 secondary, between Y1 and Y2. If 230 VAC is not present, replace TNS3 and/or 4.
  • E
    Edwin RossSep 7, 2025
    Why Trane Technologies Voyager 3 Air Conditioner economizer goes to minimum position, and will not modulate?
    • D
      David Gonzalez MDSep 8, 2025
      If your Trane Technologies Air Conditioner's economizer goes to the minimum position and won't modulate, here are potential causes: * The OAS may have failed. Check the OAS at connector P8 by disconnecting P8 from J8 on the RTRM. Check resistance between P8-1 and P8-2, refer to the Resistance versus Temperature Chart. Replace the sensor if necessary. * The DAS may have failed. Check the DAS at connector P14 of the Symbio™700 module. Check for resistance on P14 of the Symbio™700 module, refer to the Resistance versus Temperature Chart. Replace the sensor if necessary.
  • H
    Hannah DiazSep 6, 2025
    What to do if my Trane Technologies Air Conditioner power exhaust will not operate?
    • J
      Jennifer RobinsonSep 6, 2025
      If the power exhaust on your Trane Technologies Air Conditioner isn't working, here are a few potential causes: * The exhaust motor may have failed. Check the exhaust fan motor and replace it if necessary. * The XFR may have failed. Check the exhaust fan contactor (XFR) and replace it if necessary.
  • S
    Stephanie HowardSep 4, 2025
    What to do if Trane Technologies Air Conditioner ODM 3 and/or 4 will not cycle?
    • M
      Michael MorenoSep 4, 2025
      If ODM 3 and/or 4 won't cycle on your Trane Technologies Air Conditioner, here's what you can check: * The OAS may have failed. Perform an OAS Resistance/Temperature check and replace it if necessary. * There might be a failure in the wiring, terminals, or OFC3 contactor. Check these components and repair or replace them if needed. * ODM3 and/or 4 may have failed. Check the ODM and replace it if necessary. * ODF20 may have failed. Check for proper voltage and contact closure. The ODF20 relay has a 24 VAC holding coil. If voltage is present, replace the relay.
  • C
    Christian BarnettAug 21, 2025
    What to do if CPRs will not operate, but ODMs will on my Trane Technologies Air Conditioner?
    • L
      Lisa AdamsAug 21, 2025
      If the CPRs (compressor protection relays) on your Trane Technologies Air Conditioner aren't working, but the ODMs (outdoor fan motors) are, possible causes include: * A compressor failure. You should test the compressor both mechanically and electrically, and replace it if necessary. * Failure of wiring, terminals, or the mechanical contactor. Check these components and repair or replace them as needed. * LPC1 has tripped. In this case, perform a leak check, repair any leaks, evacuate the system, and recharge it. Also, check the operation of LPC1.

Summary

Introduction

Warnings, Cautions, and Notices

Provides definitions for safety advisories like WARNING, CAUTION, and NOTICE to ensure proper understanding of manual precautions.

Proper Field Wiring and Grounding

Ensures safe installation by detailing requirements for field wiring and grounding as per NEC and local codes.

Personal Protective Equipment (PPE) Required

Outlines essential PPE for technicians to prevent injury from electrical, mechanical, or chemical hazards during service.

Overview of Manual

Explains the scope of the manual, emphasizing that procedures should only be done by qualified technicians.

Model Number Description

60 Hz Model Number Breakdown

Details the meaning of each digit in the 60 Hz model number for unit identification and configuration.

50 Hz Model Number Breakdown

Details the meaning of each digit in the 50 Hz model number for unit identification and configuration.

General Information

Unit Inspection

Instructions for inspecting the unit upon receipt for shipping damage or material shortages before installation.

Storage Guidelines

Provides guidance on storing the unit in a level, dry location and taking precautions against condensate formation.

Unit Dimensions and Weights

Recommended Clearances

Specifies adequate clearances around and above the unit for proper operation and servicing access.

Unit Rigging and Placement

Details proper procedures and equipment for rigging and placing the unit safely and correctly on the curb.

Pre-Installation

General Unit Requirements

Checklists for unit receipt, rigging, curb sealing, and basic connections prior to unit installation.

Electrical Requirements

Pre-installation electrical checks and connection requirements, including warnings.

Installation General Requirements

Condensate Drain Connection

Instructions for connecting the condensate drain line, including trap installation and proper pitching for flow.

O;A Sensor and Tubing Installation

Steps for installing the outside air pressure sensor and pneumatic tubing for VAV applications.

Installation Electrical

Proper Field Wiring and Grounding

Emphasizes requirements for qualified personnel and adherence to codes for safe field wiring and grounding.

Electrical Wire Sizing and Protection

Provides calculations for MCA, MOP, and RDE to determine correct electrical service wire size and protection.

V3 System Input Devices and Functions

Describes various sensors and input devices like thermostats, humidity sensors, and zone sensors for system control.

Installation Piping

General Requirements

Covers general safety precautions, gas pressure, leak testing, and code compliance for piping installation.

Connecting the Gas Supply Line

Step-by-step guide for connecting the gas supply piping to the unit's furnace gas train, including leak testing.

Startup

Symbio Controls Startup

Guide to using the Symbio 700 Service Test Mode for energizing system components during startup.

Electrical Phasing Verification

Details the critical process of verifying and correcting electrical phasing for proper compressor operation.

Starting the Unit

Steps for powering up the unit, performing self-diagnostics, and initiating operation stages via the user interface.

Maintenance

Fan Belt Adjustment

Procedure for inspecting and adjusting supply fan belt tension using a tension gauge for proper operation.

Filters Inspection and Replacement

Instructions for inspecting, cleaning, or replacing return air filters based on unit model and filter size.

Coil Cleaning Procedures

Guidance on cleaning evaporator, condenser, and reheat coils to maintain unit efficiency, including safety precautions.

Refrigeration System

R-410 A Refrigerant Handling

Highlights safety warnings and necessary equipment for handling R-410A refrigerant due to higher operating pressures.

Refrigerant Evacuation and Charging

Outlines procedures for removing and recharging refrigerant, emphasizing proper practices to avoid compressor damage.

Compressor Oil Management

Procedures for checking compressor oil level and condition, especially after motor burnouts.

Troubleshooting

Unit Not Operating or Controlling Properly

Covers common issues like unit non-operation, lack of heating/cooling, or failure to control to set points.

Economizer and Exhaust Fan Malfunctions

Addresses issues with economizer operation, minimum position, modulation, and power exhaust fan functionality.

Unit Wiring Diagram Numbers

Warranty and Liability Clause

Trane Technologies Voyager 3 Specifications

General IconGeneral
TypeRooftop Unit
RefrigerantR-410A
DimensionsVaries by model
WeightVaries by model
Tonnage3 - 25 tons
Energy Efficiency Ratio (EER)Up to 11.2
Voltage208-230/460V

Related product manuals