18-AC51D1-10E-EN 19
STEP 3 - Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a mini-
mum of 20 minutes to stabilize before accurate
measurements can be made.
20 MIN.
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
036 & 037 Models
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
Add 5°
Add 4°
Add 2°
Add 3° of Subcooling
Add 1° of Subcooling
042 & 043 Models
Add 6°
Add 5°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
048 Models
Add 6°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
Add 6°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Add 5° of Subcooling
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Design
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
060 Models
030 & 031 Models
Add 4°
Add 3°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
018 Models
Add 3°
Add 2°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
024 & 025 Models
Add 4°
Add 2°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
For 018L, 024/25L, 030/31L, 036/37L, 036/37M, 042/43L, 048L and 060L Models: