EasyManua.ls Logo

Trane 4TTR5018N - User Manual

Trane 4TTR5018N
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
18-AC123D1-1B-EN
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANTThis Document is customer property and is to remain with this unit. Please return to service informa-
tion pack upon completion of work.
Condensing Units
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. Some of the benefits of
installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall
system reliability.
4TTR5018 – 060
Table of Contents
Section 1. Safety ..................................................................................... 2
Section 2. Unit Location Considerations ............................................. 3
Section 3. Unit Preparation.................................................................... 4
Section 4. Setting the Unit ..................................................................... 5
Section 5. Refrigerant Line Considerations ......................................... 5
Section 6. Refrigerant Line Routing ..................................................... 6
Section 7. Refrigerant Line Brazing ...................................................... 7
Section 8. Refrigerant Line Leak Check ............................................... 9
Section 9. Evacuation ............................................................................ 9
Section 10. Service Valves .................................................................. 10
Section 11. Electrical - Low Voltage ................................................... 10
Section 12. Electrical - High Voltage .................................................. 13
Section 13. Start Up.............................................................................. 13
Section 14. System Charge Adjustment............................................. 14
Section 15. Checkout Procedures ...................................................... 19
Section 16. Refrigeration Circuits........................................................20
Section 17. Wiring Diagrams................................................................22
Section 18. Pressure Curves................................................................26
Installation and Operation Manual
Question and Answer IconNeed help?

Do you have a question about the Trane 4TTR5018N and is the answer not in the manual?

Summary

Safety Information

Unit Location Guidelines

Unit Dimensions and Weight

Details unit dimensions and weight for different models, including a table.

Refrigerant Piping Specifications

Specifies maximum refrigerant line length and vertical change limits.

Optimal Unit Placement

Provides recommendations for outdoor unit placement to ensure airflow and reliability.

Coastal Installation Notes

Addresses special requirements for installations near saltwater environments.

Unit Preparation Steps

Initial Unit Setup

Details initial steps for unit preparation, including checking for damage and removal from pallet.

Unit Installation and Placement

Support Pad Requirements

Outlines requirements and considerations for installing the unit on a support pad.

Refrigerant Line Handling

Line and Valve Connection Sizes

Provides a table detailing refrigerant line and service valve connection sizes by model.

Factory Refrigerant Charge

Explains the factory charge for the outdoor unit and verification methods.

Refrigerant Line Length Calculation

Instructs users to determine and record required refrigerant line length and lift.

Vapor Line Insulation

Emphasizes the importance of insulating the vapor line and preventing contact.

Reusing Existing Lines

Provides precautions for reusing existing refrigerant lines during retrofit.

Refrigerant Line Routing

Line Routing Precautions

Details precautions for routing refrigerant lines to prevent noise and ensure proper installation.

Refrigerant Line Brazing Procedure

Brazing Refrigerant Lines

Provides step-by-step instructions for brazing refrigerant lines.

Refrigerant Leak Detection

Performing Leak Checks

Details the procedure for checking refrigerant lines for leaks using nitrogen and soap solution.

System Evacuation

Evacuating Lines and Coil

Explains the process of evacuating the system using a micron gauge.

Service Valve Operations

Opening Gas Service Valve

Provides instructions on how to open the gas service valve after checks are complete.

Opening Liquid Service Valve

Details the procedure for safely opening the liquid service valve, including warnings.

Low Voltage Electrical

Low Voltage Wire Length Limits

Defines maximum lengths for low voltage wiring based on wire gauge.

Low Voltage Wiring Diagrams

Illustrates low voltage wiring connections for various thermostat and air handler configurations.

High Voltage Electrical

High Voltage Power Requirements

Details requirements for high voltage power supply and compliance with codes.

Disconnect Switch Installation

Recommends installing a separate disconnect switch for high voltage connections.

High Voltage Grounding

Specifies grounding requirements for the outdoor unit according to codes.

System Startup

Initial System Startup

Outlines the steps for safely starting up the installed system.

System Charge Adjustment

Temperature Measurement for Charging

Explains temperature measurements needed for system charge adjustment.

Subcooling Charging Method

Provides charts and steps for adjusting system charge using subcooling method.

Weigh-In Charging Method

Details the weigh-in method for system charging when other methods are not feasible.

Post-Installation Checks

Operational and Checkout Checklist

Lists essential checks and operational procedures after installation completion.

Refrigeration Circuit Diagrams

5018 & 5024 Model Circuits

Illustrates the refrigeration circuit diagram for 5018 and 5024 model condensing units.

5030 & 5036 Model Circuits

Shows the refrigeration circuit diagram for 5030 and 5036 model condensing units.

5042 & 5048 Model Circuits

Presents the refrigeration circuit diagram for 5042 and 5048 model condensing units.

5060 Model Circuits

Displays the refrigeration circuit diagram for 5060 model condensing units.

Electrical Wiring Schematics

4 TTR5018-048 Wiring Diagram

Presents the wiring diagram for 4TTR5018 through 4TTR048 condensing units.

4 TTR5060 Wiring Diagram

Provides the wiring diagram specific to the 4TTR5060 model condensing unit.

Performance Pressure Curves

4 TTR5018 N1 Pressure Curves

Shows pressure curves for the 4TTR5018N1 model under cooling conditions.

4 TTR5024 N1 Pressure Curves

Displays pressure curves for the 4TTR5024N1 model during cooling operation.

4 TTR5030 N1 Pressure Curves

Provides pressure curves for the 4TTR5030N1 model in cooling mode.

4 TTR5036 N1 Pressure Curves

Shows pressure curves for the 4TTR5036N1 model for cooling applications.

4 TTR5042 N1 Pressure Curves

Details pressure curves for the 4TTR5042N1 model under cooling conditions.

4 TTR5048 N1 Pressure Curves

Presents pressure curves for the 4TTR5048N1 model during cooling operation.

4 TTR5060 N1 Pressure Curves

Illustrates pressure curves for the 4TTR5060N1 model in cooling mode.

Overview

This document is an Installation and Operation Manual for Trane Condensing Units, specifically models 4TTR5018 through 4TTR5060. It provides comprehensive instructions for the proper installation, startup, and maintenance of these outdoor condensing units, emphasizing compliance with national, state, and local codes. The manual is intended for individuals with adequate electrical and mechanical experience, as any attempt to repair the product without proper knowledge could result in personal injury or property damage.

Function Description:

The Trane Condensing Units are designed to be part of a central air conditioning system, working in conjunction with an indoor evaporator coil and air handler to provide cooling. These units utilize R-410A refrigerant, which operates at higher pressures than older refrigerants like R-22. The primary function of the condensing unit is to compress and condense the refrigerant, releasing heat to the outdoor environment, thereby facilitating the cooling cycle within the building. The manual stresses the importance of installing only approved matched indoor and outdoor systems to ensure maximum efficiency, optimum performance, and overall system reliability.

Usage Features:

The manual outlines several key considerations for the proper usage and installation of these condensing units. Unit location is critical, with recommendations for unrestricted top discharge areas (at least five feet clearance), three feet clearance in front of control boxes and other service-requiring sides, and a minimum of 12 inches from any wall or surrounding shrubbery to ensure adequate airflow. It also advises against locating units near bedrooms due to potential operational sounds and away from structures where roof runoff water could pour directly onto the unit. For installations within one mile of salt water, the addition of a Seacoast Kit (BAYSEAC001) is recommended.

Refrigerant piping limits are specified, with a maximum total line length of 150 feet (including lift) and a maximum vertical change of 50 feet. The manual provides detailed instructions for preparing the unit, including checking for damage upon arrival and removing the unit from its pallet by cutting securing tabs.

For electrical connections, the manual differentiates between low voltage and high voltage wiring. It provides hook-up diagrams for various indoor unit configurations (TEM 3, 4, 6, 8, TAM 4, 7, 9, and furnace systems) and specifies maximum wire lengths for different AWG sizes to ensure proper low voltage operation. For high voltage, it mandates compliance with the equipment nameplate and all national, state, and local codes, recommending a separate disconnect switch at the outdoor unit and flexible electrical conduit to minimize vibration transmission. Proper grounding of the outdoor unit is also emphasized.

The startup procedure includes ensuring all installation steps are completed, setting the system thermostat to OFF, applying power to the units, and waiting one hour before starting if a compressor crankcase heater accessory is used and the outdoor ambient temperature is below 70°F.

Maintenance Features:

The manual details critical maintenance-related procedures, particularly concerning refrigerant handling and system charging. It highlights that R-410A systems use POE oil, which readily absorbs moisture, necessitating that the system remain sealed whenever possible. If a system has been open to the atmosphere for more than four hours, the compressor oil must be replaced. It also warns against breaking a vacuum with air and always recommends changing driers when opening the system for component replacement.

Brazing of refrigerant lines is covered extensively, including deburring pipe ends, cleaning surfaces, purging with dry nitrogen to prevent oxidation, and wrapping valve bodies with wet rags to avoid heat damage. A crucial step is the refrigerant line leak check, where lines and the evaporator coil are pressurized to 150 PSIG with dry nitrogen, and all brazed locations are checked for leaks using a soapy solution. Any leaks must be repaired before proceeding.

Evacuation of the refrigerant lines and indoor coil is required until a micron gauge reads no higher than 350 microns, followed by observing the gauge to ensure it does not rise above 500 microns in one minute. The manual provides specific instructions for opening the gas and liquid service valves, emphasizing extreme caution when opening the liquid line service valve to prevent abrupt release of system charge.

System charge adjustment is a key maintenance feature, with subcooling (in cooling mode) being the recommended method for charging above 55°F ambient outdoor temperature for TXV/EEV systems. For fixed orifice systems, superheat charging is used. The manual provides detailed charts and steps for determining the correct subcooling or superheat values based on line length, lift, and indoor/outdoor temperatures. It also includes a "Weigh-In Method" for initial installations or when power is unavailable, or temperatures are outside the range for standard charging methods. The process involves measuring liquid line temperature and pressure, and then using a charging chart to determine if refrigerant needs to be added or recovered.

Finally, the manual includes a "Checkout Procedure" checklist to ensure proper operational performance after installation, including verifying leak-free refrigerant lines, proper insulation, secure and isolated lines, sealed masonry passages, tight electrical connections, smooth outdoor fan operation, free-draining indoor coil, unobstructed registers and grilles, installed return air filter, correct airflow setting, and safe operation in all modes. Pressure curves are provided at the end of the document to help verify typical performance. The document explicitly states that it is customer property and should remain with the unit, to be returned to the service information pack upon completion of work.

Trane 4TTR5018N Specifications

General IconGeneral
Model4TTR5018N
TypeHeat Pump
Cooling Capacity (tons)1.5
Cooling Capacity (BTU/h)18000
Heating Capacity (tons)1.5
Heating Capacity (BTU/h)18000
RefrigerantR-410A
Voltage208/230
Phase1
Compressor TypeScroll
StagesSingle Stage
Unit Weight (lbs)220

Related product manuals