18-BB34D1-19B-EN
27
Indoor Fan Performance
Horizontal and Downflow External Static Pressure (IN.WG)
4WC-
Y4036
DIP Switch Setting Horizontal Airflow [Down Airflow in Brackets]
Airflow
Setting
1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
350 CFM/
TON
OFF OFF OFF ON
Watts
162
[169]
173
[182]
197
[210]
226
[243]
256
[273]
285
[301]
313
[331]
343
[370]
360
[433]
- -
CFM
1058
[1025]
1062
[1062]
1063
[1068]
1063
[1063]
1062
[1060]
1060
[1061]
1057
[1064]
1053
[1055]
1010
[1015]
- -
400 CFM/
TON
(Factory
Default)
OFF OFF OFF OFF
Watts
179
[225]
230
[253]
265
[283]
296
[315]
329
[348]
366
[381]
403
[414]
431
[449]
436
[484]
- -
CFM
1179
[1187]
1196
[1201]
1204
[1203]
1206
[1201]
1205
[1198]
1203
[1197]
1199
[1194]
1194
[1184]
1185
[1157]
- -
45000
CFM/TON
OFF OFF ON OFF
Watts
318
[339]
336
[357]
365
[390]
399
[424]
435
[455]
469
[483]
502
[516]
533
[571]
- - -
CFM
1390
[1391]
1376
[1377]
1370
[1377]
1366
[1375]
1361
[1366]
1354
[1352]
1349
[1344]
1351
[1360]
- - -
4WC-
Y4048
DIP Switch Setting Horizontal Airflow [Down Airflow in Brackets]
Airflow
Setting
1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
350 CFM/
TON
OFF OFF OFF ON
Watts
187
[208]
232
[254]
264
[284]
291
[312]
318
[343]
347
[379]
379
[414]
413
[437]
446
[460]
473
[490]
-
CFM
1355
[1337]
1387
[1393]
1396
[1398]
1392
[1388]
1382
[1383]
1370
[1390]
1360
[1399]
1351
[1384]
1341
[1380]
1326
[1370]
-
400 CFM/
TON
(Factory
Default)
OFF OFF OFF OFF
Watts
315
[302]
324
[349]
352
[386]
389
[423]
428
[465]
464
[509]
498
[552]
529
[583]
563
[599]
606
[628]
-
CFM
1603
[1574]
1581
[1580]
1577
[1585]
1580
[1589]
1583
[1594]
1583
[1598]
1577
[1601]
1567
[1597]
1558
[1584]
1556
[1556]
-
45000
CFM/TON
OFF OFF ON OFF
Watts
301
[501]
431
[528]
507
[555]
552
[592]
584
[631]
615
[672]
651
[714]
694
[760]
739
[800]
779
[845]
-
CFM
1752
[1847]
1794
[1823]
1812
[1817]
1816
[1818]
1812
[1820]
1806
[1819]
1800
[1817]
1797
[1820]
1793
[1815]
1985
[1810]
-
4WC-
Y4060
DIP Switch Setting Horizontal Airflow [Down Airflow in Brackets]
Airflow
Setting
1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
350 CFM/
TON
OFF OFF OFF ON
Watts
394
[443]
427
[461]
464
[493]
504
[532]
548
[571]
591
[607]
633
[642]
668
[680]
- - -
CFM
1673
[1796]
1772
[1741]
1799
[1726]
1793
[1725]
1799
[1722]
1771
[1712]
1767
[1698]
1756
[1692]
- - -
400 CFM/
TON
(Factory
Default)
OFF OFF OFF OFF
Watts
695
[740]
642
[697]
660
[715]
710
[763]
764
[819]
811
[866]
849
[892]
893
[894]
966
[872]
- -
CFM
2054
[2010]
2036
[1987]
2031
[1779]
2032
[1977]
2033
[1976]
2031
[1969]
2023
[1950]
2012
[1913]
2002
[1852]
- -
Airflow with Auxilary Heat (CFM)
SWITCH SETTINGS SELECTION
NOMINAL AIRFLOW
4WCY4036 4WCY4048 4WCY4060
7 - OFF 8 - OFF LOW 1050 CFM 1400 CFM 1400 CFM
7 - ON 8 - OFF HIGH 1200 CFM 1600 CFM 1600 CFM
7 - OFF 8 - ON HIGH 1200CFM 1600 CFM 1600 CFM
7 - ON 8 - ON HIGH 1200CFM 1600 CFM 1600 CFM