30 UNT-SVX041D-EN
Electrical Data
Electric Heat
• An auto-reset high limit device is included. Back up
protection is also provided.
• Power connection is single point.
• The heater is located in the reheat position relative to
the cooling coil.
• The fan coil unit does not include a fuse or fusible type
disconnect. Motor sub-fusing as per electrical code.
Table 16. Electric heat - kilowatts (kW) and current draw (amps) per model for 300 unit size
Unit
Size
Connection
Voltage EH Ratings (kW/Amps)
Volts/ph/Hz kW Amps kW Amps kW Amps kW Amps kW Amps
300
(a)
120/1/60 0.5 4.2 1.0 8.3 1.5 12.5 2.0 16.7 2.5 20.8
208/1/60 0.4 1.9 0.8 3.8 1.1 5.3 1.5 7.2
240/1/60 0.5 2.1 1.0 4.2 1.5 6.3 2.0 8.3 2.5 10.4
277/1/60 0.5 1.8 1.0 3.6 1.5 5.4 2.0 7.2 2.5 9.0
(a) Size 300 units are wired for single stage operation.
Table 17. Electric heat - kilowatts (kW) and current draw (amps) per model for 400 to 1200 unit size
Unit
Size
Connection
Voltage EH Ratings (kW/Amps)
Volts/ph/
Hz kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps
400
(a)
120/1/60 2.0 16.7 2.5 20.8
208/1/60 1.5 7.2 1.9 9.1 2.3 11.1
240/1/60 2.0 8.3 2.5 10.4 3.0 12.5
277/1/60 2.0 7.2 2.5 9.0 3.0 10.8
600
(b)
120/1/60 2.0 16.7 3.0 25.0
208/1/60 1.5 7.2 2.3 11.1 3.0 14.4 3.8 18.3
240/1/60 2.0 8.3 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0
277/1/60 2.0 7.2 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7
800
120/1/60 2.0 16.7
3.0 25.0
208/1/60 1.5 7.2 2.3 11.1 3.0 14.4 3.8 18.3 4.5 21.6
240/1/60 2.0 8.3 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0 7.0 29.2
277/1/60 2.0 7.2 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7 7.0 25.3
1000
120/1/60
3.0 25.0
208/1/60 1.5 7.2 2.3 11.1 3.0 14.4 3.8 18.3 4.5 21.6
240/1/60 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0 7.0 29.2 8.0 33.3
277/1/60 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7 7.0 25.3 8.0 28.9
1200
120/1/60
3.0 25.0
208/1/60 2.3 11.1 3.0 14.4 3.8 18.3 4.5 21.6 5.3 25.5 6.0 28.8
240/1/60 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0 7.0 29.2 8.0 33.3 10.0 41.7
277/1/60 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7 7.0 25.3 8.0 28.9 10.0 36.1
(a) Size 400 units are wired for single stage operation.
(b) Sizes 600, 800, 1000, and 1200 are wired for 2 stage operation.
Amps = kW x 1000
Volts
Air temp. rise (Delta ()T) = kW x 3160
= MBh x 925
CFM CFM