Electrical Data
Electric Heat
An auto-reset high limit device is included. Back up
protection is also provided.
Power connection is single point.
The heater is located in the reheat position relative to
the cooling coil.
The fan coil unit does not include a fuse or fusible type
disconnect. Motor sub-fusing as per electrical code.
Table 16. Electric heat - kilowatts (kW) and current draw (amps) per model for 300 unit size
Unit
Size
Connection
Voltage EH Ratings (kW/Amps)
Volts/ph/Hz kW Amps kW Amps kW Amps kW Amps kW Amps
300
(a)
120/1/60 0.5 4.2 1.0 8.3 1.5 12.5 2.0 16.7 2.5 20.8
208/1/60 0.4 1.9 0.8 3.8 1.1 5.3 1.5 7.2
240/1/60 0.5 2.1 1.0 4.2 1.5 6.3 2.0 8.3 2.5 10.4
277/1/60 0.5 1.8 1.0 3.6 1.5 5.4 2.0 7.2 2.5 9.0
(a) Size 300 units are wired for single stage operation.
Table 17. Electric heat - kilowatts (kW) and current draw (amps) per model for 400 to 1200 unit size
Unit
Size
Connection
Voltage EH Ratings (kW/Amps)
Volts/ph/
Hz kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps kW Amps
400
(a)
120/1/60 2.0 16.7 2.5 20.8
208/1/60 1.5 7.2 1.9 9.1 2.3 11.1
240/1/60 2.0 8.3 2.5 10.4 3.0 12.5
277/1/60 2.0 7.2 2.5 9.0 3.0 10.8
600
(b)
120/1/60 2.0 16.7 3.0 25.0
208/1/60 1.5 7.2 2.3 11.1 3.0 14.4 3.8 18.3
240/1/60 2.0 8.3 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0
277/1/60 2.0 7.2 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7
800
120/1/60 2.0 16.7
3.0 25.0
208/1/60 1.5 7.2 2.3 11.1 3.0 14.4 3.8 18.3 4.5 21.6
240/1/60 2.0 8.3 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0 7.0 29.2
277/1/60 2.0 7.2 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7 7.0 25.3
1000
120/1/60
3.0 25.0
208/1/60 1.5 7.2 2.3 11.1 3.0 14.4 3.8 18.3 4.5 21.6
240/1/60 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0 7.0 29.2 8.0 33.3
277/1/60 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7 7.0 25.3 8.0 28.9
1200
120/1/60
3.0 25.0
208/1/60 2.3 11.1 3.0 14.4 3.8 18.3 4.5 21.6 5.3 25.5 6.0 28.8
240/1/60 3.0 12.5 4.0 16.7 5.0 20.8 6.0 25.0 7.0 29.2 8.0 33.3 10.0 41.7
277/1/60 3.0 10.8 4.0 14.4 5.0 18.1 6.0 21.7 7.0 25.3 8.0 28.9 10.0 36.1
(a) Size 400 units are wired for single stage operation.
(b) Sizes 600, 800, 1000, and 1200 are wired for 2 stage operation.
Amps = kW x 1000
Volts
Air temp. rise (Delta ()T) = kW x 3160
= MBh x 925
CFM CFM