Trane Foundation EBC180 - JADE Controls - Low Leak Economizer Sequence of Operation

Trane Foundation EBC180
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RT-SVX50J-EN
29
JADE Controls - Low Leak
Economizer Sequence of
Operation
Table 5. Dry bulb operation no DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I Y2-I FAN SPD Y1-O Y2-O
Occupied Unoccupied
None No
Off Off
High
0-v/Off 0-v/Off
MIN POS Closed
On Off
High
24-v/On 0-v/Off
MIN POS Closed
On On
High
24-v/On 24-v/On
MIN POS Closed
None Yes
Off Off
High
0-v/Off 0-v/Off
MIN POS Closed
On Off
High
0-v/Off 0-v/Off
MIN POS to Full-Open Closed to Full-Open
On On
High
24-v/On 0-v/Off
(a)
MIN POS to Full-Open Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
Table 6. Dry bulb operation with DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I Y2-I FAN SPD Y1-O Y2-O
Occupied Unoccupied
Below CO
2
set
No
Off Off
High
0-v/Off 0-v/Off
VENTMIN Closed
On Off
High
24-v/On 0-v/Off
VENTMIN Closed
On On
High
24-v/On 24-v/On
VENTMIN Closed
Yes
Off Off
High
0-v/Off 0-v/Off
VENTMIN Closed
On Off
High
0-v/Off 0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On On
High
24-v/On 0-v/Off
(a)
VENTMIN to Full-Open Closed to Full-Open
Above CO
2
set
No
Off Off
High
0-v/Off 0-v/Off
VENTMIN to VENTMAX Closed
On Off
High
24-v/On 0-v/Off
VENTMIN to VENTMAX Closed
On On
High
24-v/On 24-v/On
VENTMIN to VENTMAX Closed
Yes
Off Off
High
0-v/Off 0-v/Off
VENTMIN to VENTMAX Closed
On Off
High
0-v/Off 0-v/Off
VENTMIN to Full-Open Closed to Full-Open
On On
High
24-v/On 0-v/Off
(a)
VENTMIN to Full-Open Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
Table 7. Enthalpy operation no DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I Y2-I FAN SPD Y1-O Y2-O
Occupied Unoccupied
None No
Off Off
High
0-v/Off 0-v/Off
MIN POS Closed
On Off
High
24-v/On 0-v/Off
MIN POS Closed
On On
High
24-v/On 24-v/On
MIN POS Closed
None Yes
Off Off
High
0-v/Off 0-v/Off
MIN POS Closed
On Off
High
0-v/Off 0-v/Off
MIN POS to Full-Open Closed to Full-Open
On On
High
24-v/On 0-v/Off
(a)
MIN POS to Full-Open Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
SSttaarrtt UUpp