SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
AVERTISSEMENT DE SÉCURITÉ
L’installation et l’entretien de cet équipement doivent être assurés exclusivement par du personnel qualifié.
L’installation, la mise en service et l’entretien d’équipements de chauffage, de ventilation et de climatisation
(CVC) présentent un danger et requièrent des connaissances et une formation spécifiques. Une installation,
un réglage ou une modification inappropriés d’un équipement par une personne non qualifiée peut provoquer
des blessures graves, voire la mort. Lors de toute intervention sur l’équipement, respectez les consignes de
sécurité figurant dans la documentation, ainsi que sur les pictogrammes, autocollants et étiquettes apposés
sur l’équipement.
Installation, Operation,
and Maintenance
Important: Proper execution of the tasks outlined in this Installation, Operation, and Maintenance manual
require and assume the technician has been certified as a start up technician for the Horizon Outdoor
Air unit. This includes working knowledge of the Tracer TU program.
Horizon™ Outdoor Air Unit
Direct Gas-Fired
Model: OAB, OAG
International Inc.
KCC
OAU-SVX005C-EN
November 2019

Table of Contents

Questions and Answers

  • R
    Riley SmithAug 19, 2025
    What to do if my Trane Horizon OABD108 unit is not running?
    • R
      Russell FrenchAug 20, 2025
      If your Trane Air Conditioner unit isn't running, there are several potential causes: * There may be no power supply to the unit disconnect switch. In this case, check the power supply. * The power disconnect might have tripped; try resetting it. * A lockout alarm mode could be active. Identify and resolve the cause of the lockout alarm. * An Emergency Stop condition might exist, so check if it's activated. * The unit could be in Unoccupied mode; change the unit mode. * The discharge air sensor might have failed or is not installed. Install and connect the discharge air sensor.
  • T
    Tara BlairAug 21, 2025
    How to troubleshoot OAD Proving Switch in Trane Air Conditioner?
    • A
      Aaron Roman IIAug 22, 2025
      To troubleshoot the OAD Proving Switch on your Trane Air Conditioner, consider the following: * There may be no voltage at the actuator. Check for voltage at the actuator. * The OAD power transformer might have failed. Replace the failed OAD power transformer. * There might be no continuity through the end switch. Check continuity through the end switch.
  • B
    Brenda WilsonAug 26, 2025
    What to do if there is no compressor in my Trane Air Conditioner?
    • T
      taylor40Aug 26, 2025
      If your Trane Air Conditioner compressor isn't working, here are a few things to check: * The compressor limit switch(es) might be open. Check and close the compressor limit switch(es). * The compressor relay might not be energized or has failed. Energize or replace the compressor relay. * The conditions might not warrant a call for cooling or dehumidification. Verify if conditions require a call for cooling or dehumidification.
  • N
    Nicholas HarringtonAug 28, 2025
    How to fix wide discharge temp swings in Trane Horizon OABD108?
    • G
      gonzalezginaAug 28, 2025
      If you're experiencing wide discharge temperature swings in your Trane Air Conditioner, it could be due to: * The discharge air sensor being too close to the unit outlet. Adjust the position of the discharge air sensor to be at least 4 ft.-0 in. away from the unit outlet. * Incorrectly set min and max gas heater manifold pressures. Check and adjust the min and max gas heater manifold pressures.
  • J
    jacqueline30Aug 30, 2025
    What to do if my space is too hot, cold, or humid with Trane Horizon OABD108?
    • L
      Lisa FriedmanAug 30, 2025
      If your space is too hot, cold, or humid when using your Trane Air Conditioner, consider these potential causes: * The setpoints might not be adjusted properly. Adjust the space setpoints. * The space sensors could be incorrectly located or wired. Check and correct the location or wiring of space sensors. * A space sensor might be malfunctioning. Replace the malfunctioning space sensor.
  • C
    Courtney RamirezSep 1, 2025
    What causes indoor fan failure in Trane Horizon OABD108 Air Conditioner?
    • W
      Wayne GrahamSep 1, 2025
      If the indoor fan fails in your Trane Air Conditioner, here are some possible reasons: * The VFD might not be operating. Ensure VFD is operating. * The outdoor and/or return air dampers might not be operating properly. Check operation of outdoor and return air dampers. * The indoor fan motor could have failed. Replace or repair the indoor fan motor. * The Indoor Fan Failure Switch IFFS (pressure) might have failed. Check and repair the Indoor Fan Failure Switch. * The IFFS tubing could be damaged or not properly connected. Repair or correctly connect the IFFS tubing. * Refer to startup procedure.
  • C
    Caitlyn GarciaSep 3, 2025
    What causes Discharge Air Temp Source Failure in Trane Air Conditioner?
    • S
      Samantha JohnsSep 3, 2025
      If you're experiencing a discharge air temperature source failure with your Trane Air Conditioner, it could be due to: * BAS communication being down. Restore BAS communication. * A failed sensor or improper sensor installation. Check and replace or properly install the sensor.
  • K
    Karen LloydSep 5, 2025
    What causes Space Temp Source Failure in Trane Air Conditioner?
    • A
      Austin GravesSep 6, 2025
      If you're experiencing a space temperature source failure with your Trane Air Conditioner, it could be due to: * BAS communication being down. Restore BAS communication. * A failed sensor or improper sensor installation. Check and replace or properly install the sensor.
  • V
    Vanessa KingSep 8, 2025
    What causes OA Temp Source Failure in Trane Horizon OABD108 Air Conditioner?
    • E
      emmaramirezSep 8, 2025
      If you're experiencing an OA temperature source failure with your Trane Air Conditioner, it could be due to: * BAS communication being down. Restore BAS communication. * A failed sensor or improper sensor installation. Check and replace or properly install the sensor.
  • C
    Carl SchmidtSep 10, 2025
    What causes OA Humidity Source Failure in Trane Air Conditioner?
    • A
      amanda09Sep 10, 2025
      If you're experiencing an OA humidity source failure with your Trane Air Conditioner, it could be caused by: * BAS communication being down. Restore BAS communication. * A failed sensor or improper sensor installation. Check and replace or properly install the sensor. * Incorrect humidity wiring polarity. Check and ensure humidity wiring polarity is correct.

Summary

Introduction

Proper Field Wiring and Grounding

Emphasizes qualified personnel for safe electrical wiring and grounding.

Personal Protective Equipment (PPE)

Details mandatory PPE requirements for technicians to prevent injury during work.

Model Number Descriptions

Unit Weight and Rigging

Installation

Electrical and Drain Requirements

Covers electrical power, condensate drain configuration, and filter installation warnings.

System Configuration and Pre-Start

Startup

Direct Heating Startup Procedures

Provides a step-by-step guide for safely starting the direct heating section of the unit.

Gas Safety and Leak Testing

Emphasizes gas safety, leak testing, and avoiding open flames for gas leak detection.

Burner System Checks

Details checks for gas pressure, burner operation, and airflow for proper unit startup.

Heating Starting Sequence

Outlines the sequence of operations for the burner and associated relays during startup.

Maintenance

Alarms and Troubleshooting

Unit-Specific Alarms

Lists common alarms for TOAU UC600 systems and their troubleshooting steps.

Component Failure Modes

Details failure modes for RTRM and flame relays, with troubleshooting guidance.

Trane Horizon OABD108 Series Specifications

General IconGeneral
Model NumberOABD108
SeriesHorizon
TypePackaged Air Conditioner
Refrigerant TypeR-410A
Phase3
Voltage460V