System Configuration and Pre-Start
28 OAU-SVX005C-EN
Reports
(continued
from
previous
page)
System Setpoints
DAT High Temp Cutout 100°F 125°F 150°F Y
DAT Low Temp Cutout 35°F 35°F 50°F Y
DAT Temp Cutout Time 10 min. 10 min. 25 min. Y
Discharge Air Cooling Setpoint 55°F 55°F 75°F Y
Discharge Air Heating Setpoint 65°F 85°F 90°F Y
EVAP Leaving Temp Setpoint 45°F 53°F 70°F Y
IVFD Signal 50% 100% 100% Y
Maximum Discharge Air Temperature 70°F 90°F 100°F Y
Minimum Discharge Air Cooling Setpoint 40°F 50°F 65°F Y
Minimum Discharge Air Heating Setpoint 50°F 55°F 60°F Y
Maximum OA Damper Position 0% 100% 100% Y
Minimum OA Damper Position 0% 100% 100% Y
Occupied Space Cooling Setpoint 65°F 74°F 90°F Y
Occupied Space Heating Setpoint 60°F 70°F 75°F Y
Outdoor Air Cooling Setpoint (OACS) 70°F 75°F 85°F Y
Outdoor Air Dewpoint Setpoint (OADS) 49°F 58°F 65°F Y
Outdoor Air Heating Setpoint (OAHS) 40°F 70°F 70°F Y
Space Dewpoint Setpoint (SPDS) 50°F 59°F 68°F Y
UNOCC Space Cooling Setpoint 60°F 80°F 90°F Y
UNOCC Space Dewpoint Setpoint 49°F 65°F 68°F Y
UNOCC Space Heating Setpoint 50°F 60°F 70°F Y
System Setup
Program Control Discharge Air Control Space ControlSpace ControlY
Compressor Count 004N
Heater Count 002N
Split Manifold Burner Not Installed Installed Installed N
Return Air Damper Option Not Installed Installed Installed N
Space Temp/Humidity Sensor Installed Not Installed Installed Installed N
Heat Type No Heat|Gas Heat|Electric Heat|Other N
Alarm Reset Off Off On Y
Supply Fan Failure Reset Off Off On Y
Override Summary List of active overrides - same as selecting Override button at top of screen
All Point Report List of all points (AO/AI/BO/BI/MS/etc …) in the configuration file
About Controller Name listed is the version of the program installed in the UC600
Expansion Modules Provides status of expansion modules
TGP2 Programs List of all TGP2 programs loaded on the UC600
Data Graphs *NOT USED*
Settings
Schedules - Refer to UC600 IOM for scheduling functions
Display Preferences
Language
Date and Time
Clean Touchscreen
Table 5. Menu descriptions (continued)
Screen Menu Point List Min/Inactive Default Max/Active
BAS
Point?