61
Table 4-1
Service Test Guide for Component Operation
COMPONENT COMPONENT CONFIGURATION Occ
BEING TESTED Supply Exhaust Condenser Heat Stages
Compressor Stage Econo Exhaust VF
D
Unocc
Fan Fan Fans 1 2 3 1 2 3 4 Damper Damper IGV Output Relay
* COMPRESSOR
20 thru 30 Ton
A Off Off A-Off/B-On Off Off Off K10-Off K11-On N/A N/A Closed Closed Closed 0% Default
B Off Off A-On/B-Off Off Off Off K10-On K11-Off N/A N/A Closed Closed Closed 0% Default
40 thru 60 Ton
1A Off Off 1A-Off/1B-On Off Off Off K11-Off K3-Off K12-On K4-Off Closed Closed Closed 0% Default
2A-Off/2B-Off
1B Off Off 1A-On/1B-Off Off Off Off K11-On K3-Off K12-Off K4-Off Closed Closed Closed 0% Default
2A-Off/2B-Off
2A Off Off 1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed Closed Closed 0% Default
2A-Off/2B-On
2B Off Off 1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed Closed Closed 0% Default
2A-On/2B-Off 0%
70 thru 105 Ton
1A & 1B Off Off 1A-Off/1B-On Off Off Off K11-Off K3-Off K12-On K4-Off Closed Closed Closed 0% Default
2A-Off/2B-Off
1C Off Off 1A-On/1B-Off Off Off Off K11-On K3-Off K12-Off K4-Off Closed Closed Closed 0% Default
2A-Off/2B-Off
2A & 2B Off Off 1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed Closed Closed 0% Default
2A-Off/2B-On
2C Off Off 1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed Closed Closed 0% Default
2A-On/2B-Off
115 thru 130 Ton
1A & 1B Off Off 1A-Off/1B-On Off Off Off K11-Off K3-Off K12-On K4-Off Closed Closed Closed 0% Default
2A-Off/2B-Off
1C & 1D Off Off 1A-On/1B-Off Off Off Off K11-On K3-Off K12-Off K4-Off Closed Closed Closed 0% Default
2A-Off/2B-Off
2A & 2B Off Off 1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed Closed Closed 0% Default
2A-Off/2B-On
2C & 2D Off Off 1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed Closed Closed 0% Default
2A-On/2B-Off
** CONDENSER FANS
20 Ton
A-2B1 Off Off A-On/B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
B-2B2 Off Off A-Off/B-On Off Off Off Off Off Off Off Closed Closed Closed 0% Default
25 - 30 Ton
A-2B1 Off Off A-On/B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
B-2B2/2B3 Off Off A-Off/B-On Off Off Off Off Off Off Off Closed Closed Closed 0% Default
40 Ton
1A-2B1 Off Off 1A-On/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-Off
1B-2B2 Off Off 1A-Off/1B-On Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-Off
2A-2B4 Off Off 1A-Off/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-On/2B-Off
2B-2B5 Off Off 1A-Off/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-On
50 & 55 Ton
1A-2B1 Off Off 1A-On/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-Off
1B-2B2/2B3 Off Off 1A-Off/1B-On Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-Off
2A-2B4 Off Off 1A-Off/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-On/2B-Off
2B-2B5/2B6 Off Off 1A-Off/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-On
60 thru 75 Ton
1A-2B1 Off Off 1A-On/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-Off
1B-2B2/2B3 Off Off 1A-Off/1B-On Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-Off
2A-2B4 Off Off 1A-Off/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-On/2B-Off
2B-2B5/2B6 Off Off 1A-Off/1B-Off Off Off Off Off Off Off Off Closed Closed Closed 0% Default
2A-Off/2B-On
Refer to the next pa
g
e for applicable notes.

Table of Contents

Other manuals for Trane IntelliPak

Related product manuals