024K SERIES
SUCT.
PRESS.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
137 249 132
139
251 137
271 134
141 253 142
273 139
293 137
143
258 142
275 144
296 142
316 140
145 261 145
280 146
298 147
318 144
338 143
147 283 149
302 149
320 149
341 147
361 146
149 306 153
324 152
343 152
363 150
383 149
151 328 156
346 155
365 154
385 153
406 152
153 331 160 350 159
368 158
387 157
408 156
155 353 163 372 162
391 161
410 159
157 375 166 394 165
413 164
159 397 169 416 168
161 420 173
163
Table 10. Charging Table for 2 Ton Models
030K SERIES
SUCT.
PRESS.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
136 244 136
138
246 141
268 137
140 248 146
270 142
292 138
142
254 144
272 147
294 143
316 140
144 258 146
278 147
296 148
319 145
341 142
146 281 150
302 150
321 149
343 146
365 144
148 305 153
325 152
345 151
367 148
390 146
150 329 156
349 154
369 152
392 150
414 148
152 332 159 352 158
373 156
394 154
416 152
154 356 162 376 160
396 158
418 156
156 380 164 400 162
420 160
158 403 167 424 164
160 427 168
162
Table 11. Charging Table for 2.5 Ton Models
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if indoor air flow, entering dry bulb, or
entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
Refrigerant Charging Tables (Cooling Mode Only)