34
P0V0-SVX001-1A-EN
DEFINITION:
This fault is generated when the PM
and the IMBC informa!on is corrupted
15 Fault Code
Disconnect power
Possible causes
PM corrupted
Faulty IMBC
Disconnect power
Is 4 pin motor
communica!on
connector installed
and fully seated on
the IMBC?
Install and/or fully
seat
NO
DEFINITION:
This fault is generated when IMBC does
not see a return signal from the blower
motor
17 Fault Code
Is 12 pin connector at
the blower ves!bule
panel installed and
fully seated?
YES
Install and/or fully
seat
NO
Is 4 pin connector at
the blower installed
and fully seated?
Install and/or fully
seat
NO
YES
Verify con!nuity of all
motor wiring and replace
motor if required
YES