Picco R32 Inverter air/water heat pumps with axial fan
38
UNIT AND AUXILIARY ELECTRICAL DATA
Unit power supply V/~/Hz 400/3PH+PE/50
On board controller circuit V/~/Hz 12/1/50
Remote controller circuit V/~/Hz 12/1/50
Fan power supply V/~/Hz 400/3PH+PE/50

applied on the right side panel of the unit.
13. OPERATING LIMITS
EVAPORATOR WATER FLOW RATE





circuit.



Model
Heat pump
140 250 260 
Minimum water ow to be assured in chiller mode (condion (1) technical sheet) [l/s] 0,9 1,1 1,4 1,6
Maximum water ow to be assured in chiller mode (condion (1) technical sheet) [l/s] 2,4 2,9 3,8 4,2
Minimum ow switch water ow rate* [l/s] 0,56 0,77 0,92 0,92
Maximum ow switch water ow rate* [l/s] 0,58 0,80 0,95 0,95











AMBIENT AIR TEMPERATURE AND SUMMERISED TABLE




Water chiller mode
Room temperature Minimum -10 °C Maximum +46 °C
Water outlet temperature Minimum +5°C Maximum +20°C
Room temperature BT version Minimum -10 °C Maximum +46 °C
Water outlet temperature BT version Minimum -8 °C Maximum +20°C
Heat pump mode
Room temperature Minimum -19 °C Maximum +20°C
Outlet water temperature Minimum +25 °C Maximum +58 °C

Room temperature with water at maximum +58 °C Minimum -8 °C Maximum +24 °C