EasyManua.ls Logo

Trane RAUJ-C60 - Unit Mounting

Trane RAUJ-C60
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SS-SVX11K-EN
43
Unit Mounting
Figure 30. Mounting location
Control
Panel
80-120 Ton
1
2
3
4
5
6
7
8
Y
X
Control
Panel
Control
Panel
20-30 Ton
40-60 Ton
1
1
2
2
3
3
4
4
5
6
Y
Y
X
X
Table 7. Isolator mounting locations (in)
Unit Size
(tons)
Mounting Location
1 2 3 4 5 6 7 8
20/25/30
X 8.00 8.00 80.125 80.125 - - - -
Y 58.75 1.25 58.75 1.25 - - - -
40
X 8.00 8.00 44.125 44.125 80.25 80.25 - -
Y 87.125 1.25 87.125 1.25 87.125 1.25 - -
50/60
X 8.00 8.00 56.875 56.875 105.75 105.75 - -
Y 87.125 1.25 87.125 1.25 87.125 1.25 - -
80
X 8.00 8.00 80.125 80.125 108.125 108.125 168.25 168.25
Y 87.125 1.25 87.125 1.25 87.125 1.25 87.125 1.25
100/120
X 8.00 8.00 105.625 105.625 121.625 121.625 219.25 219.25
Y 87.125 1.25 87.125 1.25 87.125 1.25 87.125 1.25
Table 8. RAUJ point loading weights (lbs)
Unit
Size
(tons)
Mounting Location
1 2 3 4 5 6 7 8
20 475.5 383.3 403.2 311.0
25 491.2 399.3 412.2 320.3
30 491.2 399.3 412.2 320.3
40 452.3 415.7 440.3 403.7 428.3 391.8
50 365.5 331.0 427.8 393.3 700.1 650.3
60 367.2 332.8 426.0 391.6 692.5 642.9
80 798.3 462.1 786.7 450.5 785.1 448.9 772.4 436.1
100 871.1 609.5 881.0 616.2 882.6 432.1 892.5 436.8
120 988.2 614.7 948.3 587.4 941.8 583.0 901.8 555.8
IInnssttaallllaattiioonn MMeecchhaanniiccaall

Table of Contents

Related product manuals