3
General Data (230V)(60Hz)
Air Cooled Outdoor Unit
UNIT MODELS
MCA
A 86.3 111.7 145.3 163.6 212.0
PERFORMANCES
Gross Cooling Capacity
kW (MBH) 73.9 (253) 90.3 (308) 113.9 (389) 147.9 (505) 180.5 (617)
Total Compressor Power Input
kW 25.2 26.8 36.2 50.4 53.6
Refrigerant Connection Type
Refrigerant Charge approximate per circuit
RLA/LRA (each)
A 35.7/237 45.7/255 32.1/237 35.7/237 45.7/255
Face Area
2
31.06 (2.88) 35.00 (3.25) 45.36 (4.21) 57.19 (5.31) 66.66 (6.21)
3
Minimum Outdoor Air Temperature for Mechanical cooling
Standard Ambient Operating Range
High Pressure (cut out / cut in)
Low Pressure (cut out / cut in)
MCA - Minimum Circuit Ampacity is 125% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the motor RLA.
At 7 deg C SST and 35 deg C Ambient, 400V, Subcooling 8.3 K, Superheat 11.1 K.
Nominal Airflow is rated with standard air-dry coil.
398 14 / 313 21
27 7 / 45.5 7
± ±
± ±