System Configuration and Pre-Start
32 RRU-SVX01E-EN
BI 1 O/Air Damper End Switch 1 UI4.binaryValue
BI 2 Occupancy Control Input Local 1 UI5.binaryValue
BI 3 Fan Status Switch Local 1 UI6.binaryValue
BI 4 Emergency Stop Input 1 UI7.binaryValue
BO 1 2-Position OA Damper 0 BO1
(Relay).binaryValue
9 FanControlIFV48aBacNet 0
BO 2 G - INDOOR FAN 0 BO2
(Relay).binaryValue
9 FanControlIFV48aBacNet 0
BO 3 Y1 - COOLING 0 BO3
(Relay).binaryValue
8 [8, Manual Operator]
[9, DXCoolingControlDFV48aBacNet]
0
BO 4 Y2 - COOLING 0 BO4 (triac).binaryValue 8 [8, Manual Operator]
[9, DXCoolingControlDFV48aBacNet]
0
BO 5 HOT GAS REHEAT 0 XM.32.1.BO1
(Relay).binaryValue
9 BurnerControlIFV48aBacNet 0
BO 6 W - HEATING 0 XM.32.1.BO2
(Relay).binaryValue
9 BurnerControlIFV48aBacNet 0
BV 1 Fan Failure Reset (BAS) 0 Default 0
BV 2 Alarm Reset (BAS) 0 Default 0
BV 3 Occupancy Input (BAS) 0 Default 0
BV 4 Sensor Failure 1 9 AlarmsDFandIFV48aBacNet 0
BV 5 R/Air Damper 0 Default 0
BV 6 OA Damper Failure 0 9 FanControlIFV48aBacNet 0
BV 7 S/Air High Temp Cutout 0 9 AlarmsDFandIFV48aBacNet 0
BV 8 Clg HGRH Duty Mode 0 9 DutyCycleDFandIFV48aBacNet 0
BV 9 Alarm Reset 0 9 FanControlIFV48aBacNet 0
BV 10 Space SP Thumbwheel 0 Default 0
BV 11 Heating Failure 0 9 BurnerControlIFV48aBacNet 0
BV 12 Space Heat/Cool Mode 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 13 System Lock-Out Alarm 0 9 AlarmsDFandIFV48aBacNet 0
BV 14 S/Air Low Temp Cutout 0 9 AlarmsDFandIFV48aBacNet 0
BV 15 O/Air Cooling Mode 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 16 O/Air Heating Mode 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 17 O/Air Ventilation Mode 0 Default 0
BV 18 Space Temp Sensor 1 Default 1
BV 19 Space RH Sensor 1 Default 1
BV 20 Info Alarm Active 1 9 AlarmsDFandIFV48aBacNet 0
BV 21 HGRH Coil 1 Default 1
BV 22 Reset Duty Cycle Timer 0 9 DutyCycleDFandIFV48aBacNet 0
BV 23 Unoccu Dehumid Mode 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 24 Cooling Stage 1 Allowed 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 25 Cooling Stage 2 Allowed 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 26 S/A Temp Sensor Failure 1 9 AlarmsDFandIFV48aBacNet 0
BV 27 O/A Temp Sensor Failure 1 9 AlarmsDFandIFV48aBacNet 0
BV 28 O/A RH Sensor Failure 1 9 AlarmsDFandIFV48aBacNet 0
BV 29 Setpoint Source 0 Default 0
BV 30 Heating is Running 0 9 DutyCycleDFandIFV48aBacNet 0
BV 31 Cooling is Running 0 9 DutyCycleDFandIFV48aBacNet 0
BV 32 HGRH Purge Mode 0 9 DutyCycleDFandIFV48aBacNet 0
BV 33 Alarm Status 1 9 AlarmsDFandIFV48aBacNet 0
BV 34 O/Air Dehumid Mode 0 9 ModeandSetpointsDFandIFV48aPart1BacNet 0
BV 35 Indoor Fan Failure 0 9 FanControlIFV48aBacNet 0
BV 36 Fan Failure Reset 0 Default 0
Table 4. RRU UC600 points list (continued)
Point
Type
Point
Instance Point Name Value Unit Reference
Active
Priority Priority Owner
Rel