Trane RRU120 D B Series - Alarms and Troubleshooting; Flame Relay Safety Shutdown Troubleshooting

Trane RRU120 D B Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Alarms and Troubleshooting
54 RRU-SVX01F-EN
Table 15. Troubleshooting guide for flame relays during problem of safety shutdown (lockout)
Occurs In Occurs If
Initiate Period Purge card is not installed or removed
Purge card is bad
Configuration jumpers have been changed (after 200 hours)
AC line power errors occurred
Four minute INITIATE period has been exceeded
Standby Period Airflow lockout feature is enabled and the airflow switch does not close after ten seconds or within
the specified purge card timing
Flame signal is detected after 30 seconds
Ignition/pilot valve/intermittent pilot valve terminal is energized
Main valve terminal is energized
Delayed (2
nd
stage) main valve terminal is energized (RM7895C, D/EC7895C, RM7896C/D)
Internal system fault occurred
Purge card is removed
Purge card is bad
Prepurge Period Airflow lockout feature is enabled and the airflow switch opens
Ignition/pilot valve terminal is not energized
No flame present at end of PFEP
Main valve terminal is energized
Delayed main valve terminal is energized (RM7895C/D)
Internal system fault occurred
Purge card is removed
Purge card is bad
Pilot Flame Establishing Period (PFEP) Airflow lockout feature is enabled and the airflow switch does not close after 10 seconds or within
the specified purge card timing
Flame signal is detected after 30 seconds
Ignition/pilot valve/intermittent pilot valve terminal is energized
Main valve terminal is energized.
Delayed (2
nd
stage) main valve terminal is energized (RM7895C/D, EC7895C, RM7896C/D)
Internal system fault occurred
Purge card is removed
Purge card is bad