52 RTAC-SVX002A-EN
DynaView or
EasyView
Run if Auto Remote
switch is set in
TechView and Tracer
enable and if load
exists (differential to
start)*
Stop
Stop
Auto
External Auto/Stop
Stop
Auto
BAS
Auto Local or
Comm Loss
(use defaults)**
Run only if
load exists
(differential to start)
On-Line
Notes:
*Mode transition from disable to enable shall start unit if LWT>CWS regardless of differential to start. Subsequent starts during Tracer enable will
include differential to start criteria.
**if Tracer communication is lost for 15 minutes, the auto/off mode will be determined by a user defined configuration parameter to allow
1) last sent mode
2) off
3) auto
Installation Electrical
Fig. IV-07 – Arbitration owcharts of conguration points Auto/Stop External