102 RT-SVP07B-EN
CONFIGURATION Menu
Configuration - Model Num Digit 21 or 34
Rapid Restart: INSTALLED
Used With: Units with GBAS(5VDC)
Hardware Configuration - Rapid Restart
Possible Values:
INSTALLED
NOT INSTALLED
Note: Rapid Restart functionality can be inhibited by setting this
parameter to NOT INSTALLED. If set to NOT INSTALLED the unit
will perform DX staging at restart.
The following screens will be shown if there is a GBAS(5VDC)
Rapid Restart hardware configuration failure. Otherwise press
Next/Previous keys to navigate.
GBAS Configuration Hardware Has Failed
Press Enter to Reset, CANCEL to Ignore
Note: This screen is shown if the unit was configured for Rapid
Restart and the hardware configuration input on the GBAS(5VDC)
has failed or has been changed.
Press the ENTER key to accept, and review the following screen.
Check GBAS Config Hardware, Cycle Power
RETURN HERE TO CONFIRM CONFIGURATION
Note: This screen instructs the user to:
1. Turn OFF the power to the unit.
2. Inspect the GBAS(5VDC) hardware configuration input.
3. Restore the power to the Unit.
4. Return to this configuration screen and verify entry.
Press Next/Previous keys to navigate.
Configuration - Model Num Digit 34 or 31
Ventilation Override (VOM) INSTALLED
Used With: All Units
Possible Values:
NOT INSTALLED
INSTALLED Press Next/Previous keys to navigate.
Unit Model Number
Used With: All Units
Possible Values:
Model Number information as reflected
on the unit nameplate.
Note: The screen is only displayed on units with the original RTM
modules installed at the factory. If the RTM is replaced in the field
it will no longer be displayed.
Press Next/Previous keys to navigate.