28 RT-SVP07B-EN
STATUS Menu
Electric Heat: ENABLED
Stage: 6 K11: ON K12: ON K1: ON
Used With: Units w/Electric Heat
Possible Values:
Electric Heat:
ENABLED,
DISABLED By Setup,
LIMITED By Demand Limit
DISALBED By BAS/Network
Stage: 0,1,2,3,4,5,6
K*: ON, OFF
“ENABLED” indicates heat is available.
“DISABLED” indicates heating is not allowed.
“LIMITED” indicates heating is available at reduced capacity.
OR
Gas Heat: ENABLED
Stage: 2 K11: ON K12: ON K1: ON
Used With: Units w/Staged Gas Heat
Possible Values:
Gas Heat:
ENABLED,
DISABLED By Setup,
LIMITED By Demand Limit
DISALBED By BAS/Network
Stage: 0,1,2
K*: ON, OFF
“ENABLED” indicates heat is available.
“DISABLED” indicates heating is not allowed.
“LIMITED” indicates heating is available at reduced capacity.
OR
Hydronic Heat: ENABLED
Valve Position: Opening To: 100 %
Used With: Units w/Hydronic Heat
Possible Values:
Hydronic Heat:
ENABLED,
DISABLED By Setup,
LIMITED By Demand Limit
DISABLED By Low Air Temp
DISALBED By BAS/Network
Position: 0 to 100%
“ENABLED” indicates heat is available.
“DISABLED” indicates heating is not allowed.
“LIMITED” indicates heating is available at reduced capacity.
“Opening To” and ”Closing To” indicates direction.
OR
Mod Gas Heat: ENABLED
Valve Position: Opening To: 100 %
Used With: Units w/Mod Gas Heat
Possible Values:
Mod Gas Heat:
ENABLED,
DISABLED By Setup,
LIMITED By Demand Limit
DISABLED By Low Air Temp
DISALBED By BAS/Network
Position: 0 to 100%
“ENABLED” indicates heat is available.
“DISABLED” indicates heating is not allowed.
“LIMITED” indicates heating is available at reduced capacity.
“Opening To” and ”Closing To” indicates direction.
Press Next/Previous keys to navigate.