30 RT-SVP07B-EN
STATUS Menu
End of Submenu (NEXT) to Enter STATUS
Press Next/Previous keys to navigate.
COMPRESSOR STATUS SUBMENU SCREENS
Compressor Status Submenu
Press ENTER to View Data in This Submenu
Used With: Units w/DX Cooling
Press the Next key to skip this Submenu.
Note: Combinations of the following screens will be shown based on
unit cooling capacity option.
Compressor Relay K10 Locked
Disabled By Compressor Protection (MORE)
Used With: IPakI 20-30Ton DX Cooling
Possible Values:
Compressor Relay:
K10: 1
st
Compressor
K11: 2
nd
Compressor
Top Right Field:
ON, OFF, LOCKED
Bottom Field:
When ON or OFF is Shown: ENABLED
When LOCKED is Shown:
[See “Table 4. Compressor Lockout
Sources" on page 31”]
Note: There will be 2 screens shown for this configuration, one
screen for K10 and one for K11.
Press Next/Previous keys to navigate.
OR
Compressor Relay K11 Locked
Disabled By Compressor Protection (MORE)
Used With: IPakI 40-130Ton DX Cooling
Possible Values:
Compressor Relay:
K11: 1
st
Compressor
K12: 2
nd
Compressor
K3: 3
rd
Compressor
K4: 4
th
Compressor
Top Right Field:
ON, OFF, LOCKED
Bottom Field:
When ON or OFF is Shown: ENABLED
When LOCKED is Shown:
[See “Table 4. Compressor Lockout
Sources" on page 31”]
Note: There will be 4 screens shown for this configuration, one for
K11, one for K12, one for K3 and one for K4.
Press Next/Previous keys to navigate.
OR