RT-SVP07B-EN 59
SETUP Menu
Supply Air Temp Zone Reset For Heating:
Maximum Amount of Reset Applied: 10ºF
Used With: Units w/SA Heating Reset
Type Set to “ZONE”
Factory Presets: 10ºF
Possible Values: 10 to 90ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Heating:
Maximum Amount of Reset Applied: 10ºF
Used With: Units w/SA Heating Reset
Type Set to “OA”
Factory Presets: 10ºF
Possible Values: 10 to 90ºF
• Press Next/Previous keys to navigate.
VAV Box Max Stroke Time: 6 Min
Used With: VVDA Units
Factory Presets: 6 Min
Possible Values: 0 to 10 Min
• Press Next/Previous keys to navigate.
Max Occupied IGV/VFD Command: 100%
Used With: VVDA
Factory Presets: 100%
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.