RT-SVP07B-EN 63
SETUP Menu
For Dehumid OVRD Zone Temp, Use Sensor
Connected To: RTM ZONE TEMP INPUT
Used With: Units w/Dehumid. Option
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See “DWU Source Selection” Above]
Press Next/Previous keys to navigate.
For Zone Reset Function, Use Sensor
Connected To: RTM ZONE TEMP INPUT
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See “DWU Source Selection” Above]
Press Next/Previous keys to navigate.
For Rapid Restart Function, Use Sensor
Connected To: RTM ZONE TEMP INPUT
Used With: Units w/Rapid Restart
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See “DWU Source Selection” Above]
Press Next/Previous keys to navigate.
Monitor Specific Temp Input, Use Sensor
Connected To: RTM ZONE TEMP INPUT
Used With: All Units
Factory Preset: RTM ZONE TEMP INPUT
Possible Values:
[See “DWU Source Selection” Above]
Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
Press Next/Previous keys to navigate.
OUTSIDE AIR VENTILATION SETUP SUBMENU SCREENS
Outside Air Ventilation Setup Submenu
Press ENTER to Review or Adjust
Used With: Units w/Fresh Air Option
Press the Next key to skip this Submenu.
Demand Controlled Ventilation: ENABLED
DCV Setpoint Modified By Space CO2 Level
Used With: Units w/ Fresh Air
Measurement (VCM) w/DCV or OA
Damper Min Position w/DCV Installed
Factory Preset: DISABLED
Possible Values: ENABLED, DISABLED
Bottom Field:
If ENABLED: “DCV Setpoint Modified
By Space CO
2
Level”
If DISABLED: (blank)
Press Next/Previous keys to navigate.