RT-SVP07B-EN 65
SETUP Menu
Maximum OA Flow at Design Conditions
OA Normalization: 350 CCFM
Used With: Units w/Return Fan and
Fresh Air Measurement (VCM) w/DCV,
Units w/Energy Recovery Wheel Option
Factory Preset: 1 CCFM
Possible Values: 0 to Max Unit Airflow
[See “Max Unit Airflows” in Setpoints
Section Below]
• Press Next/Previous keys to navigate.
OA Flow Calibration Data
Altitude: 0 Ft.
Used With: Units w/Return Fan and
Fresh Air Measurement (VCM)
Factory Preset: 0 Ft (0 m)
Possible Values:
[See “Table 5. Flow Calibration - Altitude
Correction Factor C.F.” for assignments
below.]
This correction factor is used to adjust airflow calculations due to
density of air at different altitudes.
Table 5. Flow Calibration - Altitude Correction Factor C.F.
Feet Meters C.F. Feet Meters C.F.
0 0 1.00 5500 1650 0.91
500 150 0.99 6000 1800 0.90
1000 300 0.98 6500 2000 0.89
1500 450 0.97 7000 2150 0.88
2000 600 0.97 7500 2300 0.87
2500 750 0.96 8000 2450 0.86
3000 900 0.95 8500 2600 0.85
3500 1050 0.94 9000 2750 0.85
4000 1200 0.93 9500 2900 0.84
4500 1350 0.92 10000 3050 0.83
5000 1500 0.91
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.