RT-SVP07B-EN 67
SETUP Menu
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
FIRE
Supply Fan Off
Inlet Vanes - Closed (if equipped)
Return Fan / Exhaust Damper - Off / Closed (if equipped)
Return Fan VFD Min
OA Dampers Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode Definitions (with VOM installed)
Each of the five VOM modes have factory presets, that when initiated by a VOM contact closure, will accomplish five
predefined operations (listed below). Any of the five sequences may be user-redefined by changing the factory presets
at the unit mounted Human Interface or through Tracer.
Ventilation Override Mode A - (Unit Off)
Supply Fan Off
Inlet Vanes / VFD - Closed / 0%
Return Fan VFD Min
Return Fan / Exhaust Damper Off / Closed (if equipped)
OA Dampers Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output Deenergized
VO Relay Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mod e B - (Pressurize)
Supply Fan On
Inlet Vanes / VFD - Open / 100%
Return Fan VFD Min
Return Fan / Exhaust Damper - Off / Closed (if equipped)
OA Dampers Open
Heat - All heat stages Off (staged gas & elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output Energized
VO Relay Energized
VCM Preheater State - Off (with VCM installed)