70 RT-SVP07B-EN
SETUP Menu
Ventilation Override Definition Mode A
Heat OFF
Used With: Units w/VOM and Heat
Installed
Possible Values: OFF, IN CONTROL
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
VCM Preheater State IN CONTROL
Used With: Units w/ and OA Preheater
Function Enabled
Possible Values: OFF, IN CONTROL
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Ventilation Override Relay ENERGIZED
Used With: Units w/VOM Installed
Possible Values: ENERGIZED,
DEENERGIZED
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Enter Password to Lock Definition:
Used With: Units w/VOM Installed and
Mode Not Locked
Note: After locking a MODE (by entering the password), the displays
for that MODE becomes "Reporting" only and the definition cannot be
changed unless the Ventilation Override Module is replaced. If the
password was entered, pressing the NEXT key will scroll through the
previous screens to confirm the selected choices for each mode as
follows:
• Press Next/Previous keys to navigate.
Ventilation Override Mode A Is Locked
Supply Fan ON
Used With: Units w/VOM Mode Locked
Factory Presets: See Definitions Above
Possible Values: N/A
Note: This is “Reporting Only” display. After all of the “VOM A”
entries have been viewed or modified, the following screen will be
displayed:
• Press Next/Previous keys to navigate.
Ventilation Override Mode B
Supply Fan OFF
Used With: All Units
Factory Presets: See Definitions Above
Possible Values: ON, OFF
Note: Follow the preceding steps, used in programming Mode "A",
to program VOM Mode “B", "C", "D", and "E" if modifications are
needed.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.