80 RT-SVP07B-EN
SETUP Menu
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup Num 1 Low Ambient
Min Voltage 2.0 VDC
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 2.0 VDC
Possible Values: 0 to 10.0 VDC
OR
Actuator Setup Cond Fan VFD Ckt 1
Min Voltage 0.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup Num 1 Low Ambient
Max Voltage 10.0 VDC
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
OR
Actuator Setup Cond Fan VFD Ckt 1
Max Voltage 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 10.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup Num 1 Low Ambient
Direct/Reverse Act DIRECT ACTING
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse
Acting
OR
Actuator Setup Cond Fan VFD Ckt 1
Direct/Reverse Act DIRECT ACTING
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
• Press Next/Previous keys to navigate.