82 RT-SVP07B-EN
SETUP Menu
OR
Actuator Setup Cond Fan VFD Ckt 2
Direct/Reverse Act DIRECT ACTING
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat
Max Stroke Time 90 Sec
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is
installed
Factory Presets: 90 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat
Min Voltage 2.0 VDC
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is
installed
Factory Presets: 2 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat
Max Voltage 10 VDC
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is
installed
Factory Presets: 10 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat
Direct/Reverse Act DIRECT ACTING
Used With: All Rooftop Units and Air
Handlers Modulating Gas is installed
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse
Acting
• Press Next/Previous keys to navigate.
Actuator Setup Exh Bypass Damper
Max Stroke Time 60 Sec
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 60 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Exh Bypass Damper
Min Voltage 2.0 VDC
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 2.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.